Fire Fan
FAN 2
The sub menu consists of;
Alarm
Inhibit
For:
Alarm
Inhibit
Press Enter then use the Move Right and / or Move Left keys to select the Fire Fan that will be
controlled by the selected functions in the sub - menu .
Press Enter to access the sub – menu then Move Right and /or Move Left keys to toggle through
the sub - menu structure. Press Enter then Move Right and /or Move Left keys to select the Zone/s
that will activate or deactivate the control when it is in alarm or inhibited. Use the Move Up or
Move Down keys to set it to active or in-active. Active meaning the Zone will operate the control
where as in–active will prevent that Zone from having control.
For:
Press Enter and the cursor will flash over the number 0,1 or 2, then press the Move Up or Move
Down keys to select the required Function. Selection relies on how the inputs / outputs have been
physically wired from the Fan Termination Board as outlined below.
0:
1:
2:
FUNCTION 2
Press Enter to update the Program and then Cancel to back out of the Menu.
For:
Latch
Function
ALARM
2..................
Function
equates to a 3 wire Start / Stop, Run & Common.
equates to a 4 wire Start / Stop, Run, Stop & Common.
equates to a 5 wire Start / Stop, Run, Stop, Fault & Common.
ACF Isolate
Latch
ACF Isolate
MAN1564-3
INHIBIT
3................