Clock
To set the day and time press Enter and the day will be highlighted. Use the Move Up or Move
Down keys to step through the days of the week, then the Move Right key to access the hours and
minutes. To access each digit use the Move Right and Move Left keys and to increment each digit
use the Move Up and Move Down keys. Press Enter to set the time and thenMove Right To
access the MCP Zone Menu.
MCP Zone
Press Enter to assign the MCP to a Zone using the Move Up and / or Move Down keys to select the
Zone, ( 1- 8 ) that the MCP will be assigned to then Enter to update the Program.
Press Cancel to return to the MCP Zone menu and then Move Right to access the Outputs Menu.
Outputs
To assign Zones that will activate the monitored outputs press Enter and a sub menu will be made
available for programming. The default condition for each output is all Zones will activate all outputs.
The sub menu consists off;
Outputs
Bell
To move through the sub menu use the Move Right and Move Left keys. For each output press
Enter, then the Move Left and Move Right to select the Zones that will operate or not operate that
output. Pressing the Move Up key will set the Zone to activate the output and the Move Down key
will set the selected Zone so it does not activate the output.
WARN SYS
12345678
All 8 Zones Selected
Press Enter to Update the Program then Cancel to return to the Sub Menu and the Move Right and or
Move Left keys to move through it. Repeat the above procedure to set or change the other Outputs
as required.
MCP ZONE
2
Warn Sys
ACF
CLOCK
FR
11 : 21
ASE
Alarm
BGD ALM1
MAN1564-3
PROGRAM
UPDATED
BGD ALM2
RST/BZ
WARN SYS
12........... 78
Zones 1,2,7 and 8 Selected