Electrical Installation And Control Cables - GE AF-600 FP Design Manual

Fan and pump drive
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

4.2.2 Electrical Installation and Control Cables

Illustration 4.8: Diagram showing all electrical terminals.
Terminal number
1+2+3
4+5+6
12
13
18
19
20
27
29
32
33
42
53
54
Table 4.3: Terminal connections
Very long control cables and analog signals may, in rare cases and depending on installation, result in 50/60 Hz earth loops due to noise from mains supply cables.
If this occurs, break the screen or insert a 100 nF capacitor between screen and chassis.
Terminal description
Terminal 1+2+3-Relay1
Terminal 4+5+6-Relay2
Terminal 12 Supply
Terminal 13 Supply
Terminal 18 Digital Input
Terminal 19 Digital Input
Terminal 20
Terminal 27 Digital Input/Output
Terminal 29 Digital Input/Output
Terminal 32 Digital Input
Terminal 33 Digital Input
Terminal 42 Analog Output
Terminal 53 Analog Input
Terminal 54 Analog Input
Parameter number
E-24
E-24
-
-
E-01
E-02
-
E-03/E-20
E-04/E-21
E-05
E-06
AN-50
F-01/AN-0#CL-0#
C-30/AN-2#/CL-0#
AF-600 FP Design Guide
4
Factory default
No operation
No operation
+24 V DC
+24 V DC
Start
No operation
Common
No operation
Jog
No operation
No operation
Speed 0-HighLim
Reference
Feedback
67