2.7.12 Application Examples

The next few pages give typical examples of applications within HVAC.
2
2.7.13 Variable Air Volume
VAV or Variable Air Volume systems, are used to control both the ventilation and temperature to satisfy the requirements of a building. Central VAV systems are
considered to be the most energy efficient method to air condition buildings. By designing central systems instead of distributed systems, a greater efficiency can
be obtained.
The efficiency comes from utilizing larger fans and larger chillers which have much higher efficiencies than small motors and distributed air-cooled chillers. Savings
are also seen from the decreased maintenance requirements.
2.7.14 The AF-600 FP Solution
While dampers and IGVs work to maintain a constant pressure in the ductwork, a frequency converter solution saves much more energy and reduces the complexity
of the installation. Instead of creating an artificial pressure drop or causing a decrease in fan efficiency, the frequency converter decreases the speed of the fan
to provide the flow and pressure required by the system.
Centrifugal devices such as fans behave according to the centrifugal laws. This means the fans decrease the pressure and flow they produce as their speed is
reduced. Their power consumption is thereby significantly reduced.
The return fan is frequently controlled to maintain a fixed difference in airflow between the supply and return. The advanced PID controller of the HVAC frequency
converter can be used to eliminate the need for additional controllers.
22
Cooling coil
Heating coil
Filter
D1
D2
D3
Pressure
signal
VAV boxes
Supply fan
3
Pressure
transmitter
Flow
Return fan
Flow
3
AF-600 FP Design Guide