Quick Links

BCS Switchgear Inc.
Selection and Application Guide
2005
RELIABLE SOLUTIONS
WL Low Voltage Power
Circuit Breaker
ANSI / UL 1066 & UL 489
bcsswitchgear.com | 888.599.0486
powerful ideas
Switchgear | Circuit Breakers | Parts | Tech Support
Global network of innovation
Need Help? 888.599.0486

Advertisement

loading

Summary of Contents for Siemens WL

  • Page 1 Switchgear | Circuit Breakers | Parts | Tech Support Selection and Application Guide 2005 powerful ideas RELIABLE SOLUTIONS Global network of innovation WL Low Voltage Power Circuit Breaker ANSI / UL 1066 & UL 489 bcsswitchgear.com | 888.599.0486 Need Help? 888.599.0486...
  • Page 2 BCS Switchgear Inc. Switchgear | Circuit Breakers | Parts | Tech Support bcsswitchgear.com | 888.599.0486 Need Help? 888.599.0486...
  • Page 3 Switchgear | Circuit Breakers | Parts | Tech Support WL Circuit Breakers and Non-Automatic Switches WL Circuit Breaker WL Communication-Capable Circuit Breakers powerful ideas reliable solutions Standards and Certificates bcsswitchgear.com | 888.599.0486 Need Help? 888.599.0486 WL Selection and Application Guide • 2005...
  • Page 4 MODBUS or PROFIBUS Communications Single Bolt Motor Operator Ground Fault Protection Module External CubicleBUS I/O Module Installation Rating Plug Plug-In Open and Closed Solenoids Operations Counter Metering Function (+ wave forms and harmonics) Circuit Breaker WL Selection and Application Guide • 2005...
  • Page 5 Modified Differential Ground Fault Scheme 1/45 Accessories 1/47 Time / Current Characteristic Curves 1/51 Secondary Terminal Assignments 1/54 Technical Data for Current Transformers 1/55 Technical Data for Voltage Transformers 1/58 Outline Drawings 1/59 WL Selection and Application Guide • 2005...
  • Page 6 WL circuit breakers are Standards Breakers are equipped with closing designed for continuous - WL ANSI / UL 1066 Circuit standard vertical main bus • Motorized operating operation at 100% of their Breakers will satisfy: connections. Horizontal bus...
  • Page 7 Sets to manual switching via a key compromise selective trip (Patent Pending) 24/7/365 power availability is A unique feature of the WL trip operation. coordination with downstream critical for some systems. unit allows the system breakers.
  • Page 8 Communication via the MODBUS Communication via the Ethernet (BDA) ● standard ❍ optional 1 Fixed short-time delay only -- not available For detailed information on the electronic trip unit functions see pages 1/36 thru 1/39 WL Selection and Application Guide • 2005...
  • Page 9 Communication via the MODBUS ❍ ❍ ❍ ❍ Communication via the Ethernet (BDA) ● standard ❍ optional -- not available For detailed information on the electronic trip unit functions see pages 1/36 thru 1/39 WL Selection and Application Guide • 2005...
  • Page 10 All non-automatic switches are H, L or F-Class, therefore “H”, “L” or “F” must be chosen for position 1 in the catalog number. Breaking capacity is equal to the short time rating. Reference Technical Data on pages 1/26 thru 1/29. WL Selection and Application Guide • 2005...
  • Page 11 (alarm and trip) WLETU748 + WLLCD48 + WLGFM48 This is not a valid choice when ordering a circuit breaker. Trip units include clear plastic front cover WLTUSC55 as standard. WL Selection and Application Guide • 2005...
  • Page 12 ✓ ✓ ✓ WLRSET120 + WLBA + WLRTCS + WLAS4 ✓ ✓ ✓ ✓ WLRSET240 + WLBA + WLRTCS + WLAS4 Trip units include clear plastic front cover WLTUSC55 or WLTUSC76 as standard. WL Selection and Application Guide • 2005...
  • Page 13 WLSTCD120 + WLSTC ✓ ✓ WLSTCD240 + WLSTC Not available if the COM15 or COM16 communication module is ordered. The 2nd shunt trip is not available unless the 1st shunt trip is also ordered. WL Selection and Application Guide • 2005...
  • Page 14 Note: To order a Remote Close Coil plus Metering Function without a COM15/16 - OR - to order a Remote Close Coil plus a COM15/16 Module without a Metering Function, order the Remote Close Coil here and then order the Metering Function or the COM15/16 Module as a Z-parameter. WL Selection and Application Guide • 2005...
  • Page 15 Z-Parameter indicates additional components are included as part of the assembled breaker order. Possible Z-Parameter components can be found on pages 1/20 - 1/23 and can be identified by the symbol. N - In this position indicates no additional components. 1/11 WL Selection and Application Guide • 2005...
  • Page 16 Breaker coding provided as standard. All 15 character spaces must be utilized for a valid catalog number. An “N” should be used when additional components are not required. All primary catalog number characters must be selected. 1/12 WL Selection and Application Guide • 2005...
  • Page 17 All necessary terminal blocks (X5, X6, X8, X9) are installed as standard. continued on the next page All guide frame mounted locks are for Frame Size II and Frame Size III only. 1/13 WL Selection and Application Guide • 2005...
  • Page 18 Z-Parameter indicates additional components are included as part of the guide frame order. Possible Z-Parameter components can be found on pages 1/18 - 1/19 and can be identified by the symbol. N - In this position indicates no additional components. 1/14 WL Selection and Application Guide • 2005...
  • Page 19 Frame Size III 5000 WLC3D350 78,628 Circuit Breaker and Non-Automatic Switch Frames must be ordered as part of 1/15 an assembled catalog number as defined on pages 1/6 through 1/11. Available January 2006 WL Selection and Application Guide • 2005...
  • Page 20 Circuit Breaker and Non-Automatic Switch Frames must be ordered as part of an assembled catalog number as defined on pages 1/6 through 1/11. Includes WLFCAR50 fuse carriage Breaking capacity with external relay is equal to the short-time rating. 1/16 WL Selection and Application Guide • 2005...
  • Page 21 WL Circuit Breaker Components and Accessories UL 489 Drawout Non-Automatic Switches Description Max Ampere Rating A Interrupting Rating kA Catalog Number List Price $ H-Class Frame Size I WLH1Z308 10,151 Frame Size I 1200 WLH1Z312 12,025 L-Class Frame Size II...
  • Page 22 Includes fuses. Does not include guide frame for the fuse carriage. Factory installed only, order as a guide frame Z-Parameter. Guide frame Z-Parameter accessory. This component can be added to an assembled guide frame catalog number order. 1/18 WL Selection and Application Guide • 2005...
  • Page 23 WLEF3 WLEF2 1/19 Breakers are coded for frame rating and interrupting Guide Frame Z-Parameter accessory. This component can capacity standard from the factory. be added to an assembled guide frame catalog number order. WL Selection and Application Guide • 2005...
  • Page 24 For use if communications is not originally installed. Requires external voltage potential transformers with 120V AC secondary output. 1/20 Circuit Breaker Z-Parameter accessory. This component can be added to an assembled breaker or switch catalog number order. WL Selection and Application Guide • 2005...
  • Page 25 WL Circuit Breaker Components and Accessories Internal Accessories Shunt Trips Description Catalog Number List Price $ WLST240 24V DC WLST24 48V DC WLST48 120V AC / 125V DC WLST120 240V DC / 250V DC WLST240 Interlock Shunt Trip Continous Duty, for UL 489 only...
  • Page 26 BDA PLUS, Electronic Trip Unit parameterization interface for PC and WLBDA Ethernet connection WLBDAP 1,593 1/22 Circuit Breaker Z-Parameter accessory. This component can be added to an assembled breaker or switch catalog number order. WL Selection and Application Guide • 2005...
  • Page 27 WLCONFIG For use with WLGAUXPLUGR ring terminal secondary auxiliary connector. 1/23 Indicates a Circuit Breaker Assembled Catalog Number Z-Parameter. This component can be added to an assembled breaker or switch catalog number order. WL Selection and Application Guide • 2005...
  • Page 28 ANSI Frame Size III WLCT3 Miscellaneous Accessories Breaker Lifting Device WLLFT Circuit Breaker Hoist WLHOIST 3,400 WLLFT It is recommended that arc chutes and main contacts are changed at the same time. 1/24 WL Selection and Application Guide • 2005...
  • Page 29 Maintenance means: replacing main contacts and arc chutes (see operating instructions). M-Class main contacts can be replaced by Siemens personnel only. Do not apply breaker at 635V AC on a system with available fault current > 85kA RMS.
  • Page 30 WL Circuit Breaker Technical Data WL Non-Automatic Switches ANSI / UL 1066 Ratings Frame Size II Frame Size III Frame Rating 1600 2000 3200 3200 4000 5000 Rating Class Short-time Withstand Current (kA RMS) 50/60 Hz 0.5 s Breaking Capacity with...
  • Page 31 1 x AWG 14 terminal Maintenance consists of replacing main contacts and arc chutes (see operating instructions.) M-Class main contacts can be replaced by Siemens personnel only. For use only with Siemens supplied ring terminals (WL10RL). Fused Breaker Weights (kg/lb)
  • Page 32 WL Circuit Breaker Technical Data WL UL 489 Insulated Case Circuit Breakers Breaker Ratings Frame Size I Frame Rating 1200 Rating Class Interrupting Current I 240V (kAIR RMS) 50/60 Hz 480V 600V Short-time Withstand Current I (kA RMS) 50/60 Hz 0.5 s...
  • Page 33 1200 1600 2000 2500 3000 4000 5000 Rating Class Short-time Withstand Current (kA RMS) 50/60 Hz 0.5 s Breaking Capacity with 240V External Relay (kA RMS) 480V 50/60 Hz, 600V instantaneous trip 1/29 WL Selection and Application Guide • 2005...
  • Page 34 MOC wire connection Bare wire pressure size (Cu) max # of aux. 1 x AWG 14 terminal connecting leads x cross section (solid or stranded) 1/30 for use only with Siemens supplied ring terminals (WL10RL) WL Selection and Application Guide • 2005...
  • Page 35 MOC wire connection Bare wire pressure size (Cu) max # of aux. 1 x AWG 14 terminal connecting leads x cross section (solid or stranded) 1/31 for use only with Siemens supplied ring terminals (WL10RL) WL Selection and Application Guide • 2005...
  • Page 36 MOC wire connection Bare wire pressure size (Cu) max # of aux. 1 x AWG 14 terminal connecting leads x cross section (solid or stranded) 1/32 for use only with Siemens supplied ring terminals (WL10RL) WL Selection and Application Guide • 2005...
  • Page 37 MOC wire connection Bare wire pressure size (Cu) max # of aux. 1 x AWG 14 terminal connecting leads x cross section (solid or stranded) 1/33 for use only with Siemens supplied ring terminals (WL10RL) WL Selection and Application Guide • 2005...
  • Page 38 AC / DC VA / W 15 / 15 Minimum shunt trip actuation signal at rated voltage Opening time of the circuit breaker at rated voltage Short circuit protection Smallest permissible fuse 1/34 WL Selection and Application Guide • 2005...
  • Page 39 Rated operational current, making Rated operational current, breaking Direct current Rated operational voltage 48V, 125V 250V Rated operational current, continuous Rated operational current, making 0.22A 0.11A Rated operational current, breaking 0.22A 0.11A Available July 2005 1/35 WL Selection and Application Guide • 2005...
  • Page 40 – – per CubicleBUS module ✔ available Extended Instantaneous Protection (EIP) allows the WL breaker to be applied at the withstand rating of the breaker with minus 0% tolerance; that means no instantaneous override whatsoever. EIP further – not available...
  • Page 41 Frame Size III 0… 1 1000… 1600 100A 400A 1… 100 1600… 10000 300A 600A 100… 500 10000… max 1000 600A 800A 500… 1000 900A 1000A 1200A 1200A ✔ available – not available optional 1/37 WL Selection and Application Guide • 2005...
  • Page 42 CubicleBUS module per CubicleBUS module ✔ available Extended Instantaneous Protection (EIP) allows the WL breaker to be applied at the withstand rating of the breaker with minus 0% tolerance; that means no instantaneous override whatsoever. EIP further – not available...
  • Page 43 +/- 2% Overvoltage +/- 2% (80… 120% V (Q) at 1 x I +/- 3% Undervoltage +/- 2% (80… 120% V Under/Over Frequency +/- 0.1 Hz ✔ available – not available optional 1/39 WL Selection and Application Guide • 2005...
  • Page 44 Protection” (Patent Pending). ‘Instantaneous’ function. The it compromises the A further benefit offered by EIP, It allows the WL breaker, as a justification for this delay is coordination benefit because over a standard LS trip unit family, across the entire range...
  • Page 45 Same as for ETU725 plus the following: • Selectable neutral conductor protection • Integrated ground fault protection, 3- or 4- wire residual only For technical details, see table on pages 1/36 and 1/37. 1/41 WL Selection and Application Guide • 2005...
  • Page 46 – CubicleBUS integrated. Features: Same as for ETU745 without the Instantaneous short-circuit trip function. For technical details, see table on pages 1/38 and 1/39. 1/42 WL Selection and Application Guide • 2005...
  • Page 47 Option: Ground fault module Ground fault alarm Ground fault trip Space for recording setting values Field addable setting values Test pushbutton Clear trip cause indicator pushbutton TEST QUERY CLEAR Query pushbutton Test socket NSE00960 1/43 WL Selection and Application Guide • 2005...
  • Page 48 3- phase currents and the neutral conductor current. Ground fault module GFM A 745-748 Ground fault module GFM AT 745-748 Ground fault module GFM A 755-776 Ground fault module GFM AT 755-776 1/44 WL Selection and Application Guide • 2005...
  • Page 49 WL Circuit Breaker Circuit Breaker Modified Differential Ground Fault Protection using WL Circuit Breakers and extra iron-core CTs Neutral Sensor for modified differential ground fault for Frame Size II 1200:1 WLGMDGFCT2 for Frame Size III 1200:1 WLGMDGFCT3 Neutral Sensor for source ground return...
  • Page 50 Locking device guide rail Door interlocking guide frame (option) Locking device in DISCONNECT position (option) 10 Guide rail 11 Shutter operating device (option) 12 Interlocks (option) 13 Position signaling switch (option) 14 Secondary disconnects 1/46 WL Selection and Application Guide • August 2005...
  • Page 51 0.2 to 3.2 s delay. to close over a signal contact is also available. If the circuit breaker is operated through communication, this signal switch is fitted as standard. 1/47 WL Selection and Application Guide • 2005...
  • Page 52 Shutter contact strips match the laminated contacts of the guide The cover strips of the shutter frame (see picture above). lock the laminated contacts of 1/48 WL Selection and Application Guide • 2005...
  • Page 53 Plexiglas cover are available for Frame Size II and Frame Size III circuit breakers. 1/49 WL Selection and Application Guide • 2005...
  • Page 54 Padlockable Sealing (Standard) Cover, Up to 3 Padlocks (WLLKKT) Mechanical CLOSE Padlockable Sealing Cover, Up to 3 Padlocks Guide Rails (WLLKKT) (Standard) Manual Charging Lever (Standard) Racking Handle Up to 3 Padlocks 1/50 (Standard) WL Selection and Application Guide • 2005...
  • Page 55 To obtain a complete release opening time is prolonged by characteristic, the appropriate about 3 to 10 ms, depending on characteristic functions must the value of the overcurrent. be determined. ETU725 and ETU727 1/51 WL Selection and Application Guide • 2005...
  • Page 56 WL Circuit Breaker Time / Current Characteristic Curves Tripping Characteristics ETU745 ETU748 1/52 WL Selection and Application Guide • 2005...
  • Page 57 WL Circuit Breaker Time / Current Characteristic Curves Tripping Characteristics ETU776 Ground Fault Curve for ETU745, 748, 755 and 776 1/53 WL Selection and Application Guide • 2005...
  • Page 58 WL Circuit Breaker Application Data WL Secondary Terminal Assignments 1/54 WL Selection and Application Guide • 2005...
  • Page 59 0.125 for dimension over 18" Regulatory Agency Approval: Notes: UL and CUL For external metering. Up to 2 CTs per guide frame (one load side, one line side) Mounts inside the guide frame. 1/55 WL Selection and Application Guide • 2005...
  • Page 60 Continuous Thermal Current Rating Factor: 0.09 for dimension between 6" & 18" 1.33 @ 30º C ambient; 1.00 @ 55º C ambient 0.125 for dimension over 18" Regulatory Agency Approval: UL and CUL 1/56 WL Selection and Application Guide • 2005...
  • Page 61 Continuous Thermal Current Rating Factor: 0.09 for dimension between 6" & 18" 1.33 @ 30º C ambient; 1.00 @ 55º C ambient Thermal Short-time Rating: (see table) Regulatory Agency Approval: UL and CUL 1/57 WL Selection and Application Guide • 2005...
  • Page 62 WL Circuit Breaker Technical Data for Voltage Transformers VT / PT Connections for the WL Breaker when equipped with Metering (WLMETER, WLMETERP) The metering module (“Meter All three VTs should be rated for VT Accuracy: Function”) can be set to expect...
  • Page 63 WL Circuit Breaker Outline Drawings Frame Size I Fixed Mounted Circuit Breaker 1/59 WL Selection and Application Guide • 2005...
  • Page 64 WL Circuit Breaker Outline Drawings Frame Size l Fixed Mounted Circuit Breakers Vertical Bus Connectors Bus Stubs (standard) Vertical Bus Connectors (optional) Top View (with optional vertical connectors) Back View 1/60 (with optional vertical connectors) WL Selection and Application Guide • 2005...
  • Page 65 WL Circuit Breaker Outline Drawings Frame Size l Fixed Mounted Circuit Breakers Front Connectors Front Connectors with Pressure Front Connectors Wire Main Connectors 1/61 WL Selection and Application Guide • 2005...
  • Page 66 WL Circuit Breaker Outline Drawings Frame Size l Fixed Mounted Circuit Breakers Door Cut-outs Door Cut-out Door Cut-out (middle escutcheon visible) Door Cut-out (center escutcheon visible) 1/62 WL Selection and Application Guide • 2005...
  • Page 67 WL Circuit Breaker Outline Drawings Frame Size II Fixed Mounted Circuit Breaker (with optional vertical bus connectors) Table 1 (see Table 2) Table 2 1/63 WL Selection and Application Guide • 2005...
  • Page 68 WL Circuit Breaker Outline Drawings Frame Size II Fixeded Mounted Circuit Breaker Alternate Bus Connectors (see Table 1) Bus Stubs (standard) Bus Stubs (Standard) Vertical Bus Connectors (optional) Vertical Bus Connectors (optional) Table 1 1/64 WL Selection and Application Guide • 2005...
  • Page 69 WL Circuit Breaker Outline Drawings Frame Size II Fixed Mounted Circuit Breaker Front Connectors Front Connectors with Pressure Wire Main Connectors 1/65 WL Selection and Application Guide • 2005...
  • Page 70 WL Circuit Breaker Outline Drawings Frame Size lII Fixed Mounted Circuit Breaker Bus Stubs (Standard) Vertical Bus Connectors (optional) 1/66 WL Selection and Application Guide • 2005...
  • Page 71 WL Circuit Breaker Outline Drawings Frame Size lII Fixed Mounted Circuit Breaker Alternate Bus Connectors Top View (with optional vertical connectors) Top View (with standard bus stubs) 1/67 WL Selection and Application Guide • 2005...
  • Page 72 WL Circuit Breaker Outline Drawings Frame Size lII Fixed Mounted Circuit Breaker 1/68 WL Selection and Application Guide • 2005...
  • Page 73 WL Circuit Breaker Outline Drawings Frame Size lII Fixed Mounted Circuit Breaker Front Connectors 1/69 WL Selection and Application Guide • 2005...
  • Page 74 Frame Size lI & Frame Size III Fixed Mounted Circuit Breaker Door Cut-outs Door Cut-out with Edge Protector (cut-out dimensions shown are with the edge protector installed) Door Cut-out (middle escutcheon visible) Door cut-out (center escutcheon visible) 1/70 WL Selection and Application Guide • 2005...
  • Page 75 WL Circuit Breaker Outline Drawings Frame Size I UL 489 Draw-out Circuit Breaker 1/71 WL Selection and Application Guide • 2005...
  • Page 76 Frame Size I UL 489 Draw-out Circuit Breaker Door Cut-out with Edge Protector (cut-out dimensions shown are with the edge protector installed) Door Cut-out (middle escutcheon visible) Door cut-out (center escutcheon visible) 1/72 WL Selection and Application Guide • 2005...
  • Page 77 WL Circuit Breaker Outline Drawings Frame Size I UL 489 Draw-out Circuit breaker Plexiglas Cover 1/73 WL Selection and Application Guide • 2005...
  • Page 78 N, S, H and L- Class Note: The main bus stabs shown here are for the 800A and 1600A Frame Size II breakers. See page 1/33 for other frame ratings and horizontal bus configuration. 1/74 WL Selection and Application Guide • 2005...
  • Page 79 Horizontal Main Bus Connectors are only available for N, S, or H-Class breakers and can only be ordered as a factory installed Z-Parameter as part of an assembled guide frame catalog number order. 1/75 WL Selection and Application Guide • 2005...
  • Page 80 N, S, H and L- Class Door Cut-out with Edge Protector (Cut-out dimensions shown are with the Edge Protector installed) Door Cut-out with the Middle Escutacheon Visible Minimal Door Cut-out (Only the center escutacheon is visible) 1/76 WL Selection and Application Guide • 2005...
  • Page 81 WL Circuit Breaker Outline Drawings Frame Size II 800A, 1600A, 2000A F- Class (with fuses) 1/77 WL Selection and Application Guide • 2005...
  • Page 82 F- Class (with fuses) Door Cut-out with Edge Protector (Cut-out dimensions shown are with the Edge Protector installed) Door Cut-out with the Middle Escutcheon Visible Minimal Door Cut-out (Only the center escutcheon is visible) 1/78 WL Selection and Application Guide • 2005...
  • Page 83 WL Circuit Breaker Outline Drawings Frame Size III 3200A, 4000A, 5000A H, L and M - Class 1/79 WL Selection and Application Guide • 2005...
  • Page 84 H, L and M- Class Door Cut-out with Edge Protector (Cut-out dimensions shown are with the Edge Protector installed) Door Cut-out with the Middle Escutcheon Visible Minimal Door Cut-out (Only the center escutcheon is visible) 1/80 WL Selection and Application Guide • 2005...
  • Page 85 WL Circuit Breaker Outline Drawings Frame Size III - Fuse Carriage and Fuse Carriage Guide Frame 3200A, 4000A, 5000A F - Class 1/81 WL Selection and Application Guide • 2005...
  • Page 86 WL Circuit Breaker Outline Drawings Frame Size III - Fuse Carriage and Fuse Carriage Guide Frame 3200A, 4000A, 5000A F - Class Door Cut-out with Edge Protector 1/82 WL Selection and Application Guide • August 2005...
  • Page 87: Table Of Contents

    Communication-capable Circuit Breaker Advantages through Communication Connection Diagram Communication Modules I/O CubicleBUS Modules Breaker Data Adapter Supervisory Software WinPM.Net ™ 2/10 WL Selection and Application Guide • 2005...
  • Page 88: Advantages Through Communication

    PLC or computer. switching on and off of plant equipment *Short Message Service (SMS) is the transmission of short text messages to and from a mobile phone, fax machine, and/or IP address. WL Selection and Application Guide • 2005...
  • Page 89: Connection Diagram

    WL Circuit Breakers opportunities to reduce MODBUS, PROFIBUS or via and accessories allows secondary device count Ethernet/Intranet/Internet. simple retrofitting of all and wiring and to increase communication components. functionality implemented in switchgear. WL Selection and Application Guide • 2005...
  • Page 90: Communication Modules

    ETU745, ETU748, ETU755, ing of a WL Circuit Breaker that access to information and the switchgear. and ETU776 trip units. does not yet have commun- response to events.
  • Page 91 WL Communication-capable Circuit Breaker WL Circuit Breaker Data that can be Transmitted via MODBUS, PROFIBUS or the Breaker Data Adapter (BDA) All WL Circuit Breakers with ETU745, ETU748, ETU755, ETU776 (CubicleBUS Integrated) Transmittable Circuit Breaker Data COM16/15 Application Options Transmission of Circuit Breaker Data to MODBUS via COM16 or PROFIBUS via COM15 and ●...
  • Page 92: I/O Cubiclebus Modules

    ZSI module. Thus, only the closest upstream circuit breaker will be opened. The circuit breakers are inter- connected by these modules. In the event of a short circuit, WL Selection and Application Guide • 2005...
  • Page 93: Breaker Data Adapter

    ETU. The BDA includes a parameter configuration device based on documentation function making it an integrated web server for the simple to print a listing of all WL configuration, operation and system parameters. monitoring of WL Circuit Breakers. The BDA Plus has all the functions Breaker Data Adapter –...
  • Page 94 Interface (or BDA Plus) In this mode the BDA is used as the An additional class 2, 24V DC power local interface to the WL Breaker by supply is necessary to power the temporarily connecting it directly to BDA should the WL Breaker not the ETU.
  • Page 95: Supervisory Software Winpm.net

    – and decide on the Preventive Maintenance best corrective actions. By Base your maintenance schedule monitoring circuits 24 hours a on actual operating history. day, you can develop strategies to avoid interruptions. WL Selection and Application Guide • 2005...
  • Page 96 WL Communication-capable Circuit Breaker WL Circuit Breaker Notes 2/10 WL Selection and Application Guide • 2005...
  • Page 97 WL Circuit Breaker Standards and Certificates WL Selection and Application Guide • 2005...
  • Page 98 WL Circuit Breaker Annex Standards and Certificates WL Low Voltage Power Circuit Breakers are designed to comply with the following standards: ANSI / IEEE: C37.13, C37.16/ 16A, C37.17, C37.50, C37.100, C37.90, C37.90.1, C37.90.2 ANSI / UL: 1066 Note: In this document, “ANSI certified” means the product meets the requirements of UL1066 and ANSI C37.
  • Page 99 WL Circuit Breaker Notes WL Selection and Application Guide • 2005...
  • Page 100 WL Circuit Breaker WL Circuit Breaker Notes WL Selection and Application Guide • 2005...
  • Page 101 WL Circuit Breaker Notes WL Selection and Application Guide • 2005...
  • Page 102 WL Circuit Breaker Notes WL Selection and Application Guide • 2005...
  • Page 103 WL Circuit Breaker WL Selection and Application Guide • 2005...
  • Page 104 © 2005 Siemens Energy & Automation, Inc. All Rights Reserved Siemens is a registered trademark of Siemens AG. Product names mentioned may be trademarks or registered trademarks of their respective companies. Specifications are subject to change without notice. Order # CBSA-00001-0804...