This procedure uses the RESET button on the RMC to restart the device. It causes the device to restart
with the running (warm) configuration. If the RMC is installed inside an enclosure, you must have
access to the interior of the enclosure to access the RMC switch.
To complete a warm restart using the reset button:
1.
Lift the cover over the TFIO ports.
2.
Press and release the Reset button
Figure 8-29: Reset button
Observe the display. The LCD shows that the unit is shutting down and restarting.
IMPORTANT NOTE: If the RMC seems does not restart, press and hold the Reset button for eight
seconds.
8.5.3

Warm restart from the device loader

This procedure performs the warm restart from the 32-bit loader. The procedure can be performed
while on a local or remote Loader connection.
The procedure causes the device to restart with the running (warm) configuration.
To complete a warm restart from the device loader:
1.
Launch PCCU.
Click the 32 Bit Loader icon in the toolbar. A message box displays.
2.
Click Yes.
3.
4.
Verify or type the connection setup parameters and click Connect. The Loader screen displays.
Click Services>Restart. Select Restart using Running (Warm) configuration from the
5.
drop-down list
(Figure
1 9 0 | R MC-1 00 | 2 10 5 55 2MN A E
(Figure
8-29).
8-30).