Article number
–
Security policies
–
User authentication
–
GDS support (certificate management)
Number of sessions, max.
–
–
Number of accessible variables, max.
Number of registerable nodes, max.
–
–
Number of subscriptions per session,
max.
Sampling interval, min.
–
–
Publishing interval, min.
–
Number of server methods, max.
–
Number of inputs/outputs per server
method, max.
–
Number of monitored items, max.
Number of server interfaces, max.
–
Number of nodes for user-defined server
–
interfaces, max.
•
Alarms and Conditions
–
Number of program alarms
–
Number of alarms for system diagnostics
Further protocols
•
MODBUS
Isochronous mode
Equidistance
Jitter, max.
S7 message functions
Number of login stations for message functions,
max.
Program alarms
Number of configurable program messages,
max.
Number of loadable program messages in RUN,
max.
Number of simultaneously active program alarms
Number of program alarms
•
•
Number of alarms for system diagnostics
Number of alarms for motion technology
•
objects
Test commissioning functions
Joint commission (Team Engineering)
SIMATIC Drive Controller
Equipment Manual, 11/2022, A5E46600370-AC
6ES7615-4DF10-0AB0
Available security policies: None, Basic128Rsa15, Basic256Rsa15,
Basic256Sha256
"anonymous" or by user name & password
Yes
64
200 000
50 000
50
10 ms
10 ms
100
20
10 000; for 1 s sampling interval and 1 s send interval
10 of each "Server interfaces" / "Companion specification" type and
20 of the type "Reference namespace"
30 000
Yes
400
200
Yes; MODBUS TCP
Yes
1 µs
64
Yes
10 000; Program messages are generated by the "Program_Alarm"
block, ProDiag or GRAPH
5 000
4 000
1 000
480
Yes; Parallel online access possible for up to 10 engineering systems
Technical specifications
6ES7615-7DF10-0AB0
77