Huawei UPS5000-E-12 User Manual page 197

Table of Contents

Advertisement

UPS5000-E-(40 kVA-320 kVA)
User Manual
Figure 5-55 Associated intelligent power supply parameters on the LCD (6)
Table 5-2
Table 5-2 Associated intelligent power supply parameters
Parameter
Working mode
D.G. mode
Intra-rack power unit
start delay (s)
Input adaptability
Output freq. track rate
(Hz/s)
D.G. connection [GEN]
MUS05A DO_4
ATS
D.G. startup batt. volt.
(V/cell)
D.G. power limiting
(kVA)
D.G. charger power ratio
Issue 10 (2015-09-15)
lists the associated intelligent power supply parameters.
Value
ECO
Enabled
5
Strong
0.6
Enabled
D.G. control
Connected
1.80
N/A
N/A
In battery mode (not battery test state), when the battery voltage reaches D.G. startup batt. volt. or
Low battery voltage, the UPS triggers D.G. startup signals.
In normal mode or bypass mode, if the mains is normal (the mains supplies power for 1 minute and
the D.G. runs for 15 minutes), the UPS triggers D.G. shutdown signals.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Operations
Remarks
N/A
You cannot change the value.
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Indicates the actual D.G.
power. Set it as required.
Indicates the percentage of the
battery power provided by the
charger. Set it as required.
188