UPS5000-E-(40 kVA-320 kVA)
User Manual
The Maint. breaker closed alarm is displayed in the alarm list, as shown in
UPS transfers to maintenance bypass mode.
Figure 5-30 Locked maintenance bypass switch
Figure 5-31 Turning on the maintenance bypass switch (UPS5000-E-200K-F200)
Issue 10 (2015-09-15)
For the UPS5000-E-120 kVA and UPS5000-E-200 kVA, the maintenance bypass switch
is OFF by default and the handle points right horizontally. Turn on the switch by turning
the handle clockwise 90 degrees until it points to the ground, as shown in
For the UPS5000-E-320 kVA, the maintenance bypass switch is OFF by default and the
handle points to the ground. Turn on the switch by turning the handle clockwise 90
degrees until it points left horizontally, as shown in
UPS5000-E-320K-F320) and
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Figure 5-32
Figure 5-33
(for the UPS5000-E-320K-F320T).
5 Operations
Figure
5-31.
(for the
Figure
5-34. The