Parameter description
6.7 Output terminal
Code
Description
AO1 output
F7.22
range selection
AO2 output
F7.23
range selection
F7.24 Gain of AO1
F7.25 Gain of AO2
DO Max. output
F7.26
pulse freq.
@DO Min.
F7.27
output pulse
freq.
Auxiliary pump
F7.28
start lag time
Auxiliary pump
F7.29
stop lag time
F7.30 DO Max. output
FDT/RUN signal
F7.31
Jog selection
SINAMICS V50 converter
51
Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB
Setting range
11: AI1 (0 ~ 10V)
12: AI2
(0~10V/4~20mA)
13: Pulse
frequency
14:
Communication
setting
15: Reserve
16: Current
output (0~2 time
rated value)
0: ~10V/0~20mA
1: ~10V/4~20mA
0: ~10V/0~20mA
1: ~10V/4~20mA
1 ~200%
1~200%
DO Min. output
pulse freq. ~
50.00kHz
0.00 ~ DO Max.
output pulse freq.
0~ 9999s
0~ 9999s
0: 50.00kHz
1: 500.0Hz
0: Include Jog
signal
1: Do not
include Jog
signal
Default
Modify
0
о
0
о
100%
о
100%
О
10.00kHz
о
0.00kH z
о
0
о
0
о
0
X
0
X
Modbus
Address
0816H
0817H
0818H
0819H
081AH
081BH
081CH
081DH
081EH
081FH