Chapter 1. Overview

Figure 3: Timeline for Successful MRP Ring Repair at 16ms I/O Update Rate

MRP Operation at I/O Update Rates less than 16ms
The RX3i CEP Carrier implementation of MRP supports LinkUp/LinkDown detection, an optional part of the
MRP standard. This allows an MRC experiencing a network link failure or recovery to send LinkUp/LinkDown
messages to the MRM immediately. The MRM can heal the network without needing to wait for multiple test-
packet timeouts to detect the failure. This feature allows the network recovery time to be significantly
shorter than the test packet timeout interval because the break is detected immediately.
Minimum I/O Rate when Configured in an MRP Ring
The minimum I/O rate that is possible for bumpless operation depends on the speed and the type of physical
connection being used for the MRP ring ports. The RX3i PROFINET IO Controller supports a specified number of
GE Automation & Controls PROFINET I/O devices running at or above the minimum I/O Update Rate listed in
the following table.
For RX3i PNC operating specifications, refer to the PACSystems RX3i & RSTi-EP PROFINET I/O Controller
Manual, GFK-2571.
For operating specifications of the embedded PNC function of the RXi Controller, refer to the PACSystems RXi
ICRXICTL000 Distributed I/O Controller User's Manual, GFK-2816.
Minimum I/O Rates for Bumpless RX3i CEP Recovery
RX3i CEP Catalog Number
Minimum I/O Update Rate
100 Mb/s
Number of Devices
IC695CEP001
1ms
8
8
PACSystems* RX3i CEP PROFINET Scanner
GFK-2883E