General R/C Setup; Frost Protection - Toshiba RBC-MTSC2 Installation Manual

Mini touch screen controller with 7-day scheduler
Hide thumbs Also See for RBC-MTSC2:
Table of Contents

Advertisement

RBC-MTSC2 Mini Touch Screen Controller
6.4.3.

General R/C Setup

Enable or disable: header unit; show setpoint to 0 or 1 decimal place, frost protection.
The service information is currently only editable via the PC configuration tool.
6.4.4.

Frost Protection

Note:
It is recommended that the temperature sensor in the controller is selected for the
return air reading, due to the possibility of invalid readings from the indoor unit
sensor while the fan is not running.
Once enabled, the return air temperature will be constantly monitored, and the following strategy is
executed...
Frost Protection State
Inactive
Active
Return Air Temperature
< 8.0°C
>=10.0°C
12
Installation & Owner Manual
Action
1) Save current indoor unit state
2) Set indoor unit as follows...
On, Heating, SP=21°C
3) Frost Protection State=Active
1) Restore indoor unit state
2) Frost Protection State=Inactive