Protection And Monitoring - Siemens SITOP UPS1600 Equipment Manual

Hide thumbs Also See for SITOP UPS1600:
Table of Contents

Advertisement

Technical data

8.5 Protection and monitoring

8.5
Protection and monitoring
6EP4134-3AB00- ... (10 A)
Current limitation
30 A
Typ.
Power boost with 300 % I
Remark
for typ. 30 ms
Short-circuit protec-
Shutdown after 30 ms
tion
Reverse polarity pro-
With respect to the input voltage U
tection
Overload/short-circuit
Yes, restart in normal operation
indicator
6EP4131-
0GB00-0AY0
(1.2 Ah)
Short-circuit
Yes, fuse
protection
Reverse polarity
Yes
protection
6EP4132-
0JA00-0AY0
(2.5 Ah)
Short-circuit
Yes, fuse
protection
Reverse polarity
Yes
protection
244
6EP4136-3AB00- ... (20 A)
60 A
Power boost with 300 % I
out rated
for typ. 30 ms
and with respect to batteries
in
6EP4132-
6EP4133-
0GB00-0AY0
0GB00-0AY0
(2.5 Ah)
(3.2 Ah)
6EP4133-
6EP4134-
0GA00-0AY0
0JA00-0AY0
(3.2 Ah)
(7.5 Ah)
6EP4137-3AB00- ... (40 A)
120 A
Power boost with 300 % I
out rated
for typ. 30 ms
6EP4133-
6EP4134-
0JB00-0AY0
0GB00-0AY0
(5 Ah)
(7 Ah)
6EP4135-
0GE00-0AY0
(12 Ah)
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
out rated
6EP4135-
0GB00-0AY0
(12 Ah)
6EP4137-
0GE00-0AY0
(38 Ah)