Retransmissiontimer
Retransmissioncounter
Retransmissionmode
1070 072 196-101 (00.06) GB
Default: 200 ms
This time value determines the repeat time of a message.
If, e.g., a request message is not answered with a response message, the
request message is repeated after the retransmission time has elapsed.
Example for an entry in the configuration file:
Retransmissiontimer: 400
Default: 16
The counter determines how often a message is repeated before an error
message is sent back to the controller.
Example for an entry in the configuration file:
Retransmissioncounter: 20
Default: 0
; constant repeat time
The retransmission mode defines if the time between the repeat messages
is always the same or if the length of an interval from the previous to the next
repeat message is doubled.
Example for an entry in the configuration file:
Retransmissionmode: 1
; corresponds to 400 ms
; max. 20 repeats
; 0 = constant time interval
; 1 = doubling of the time intervals
Hardware
2- -15