FusionModule500 Smart Mini Data Center
User Manual
Item
Output frequency
General input
UPS input
Battery power distribution
Air conditioner power distribution
UPS output
UPS bypass
Output branch
Dimensions (H x W x D)
3.2.4 (Optional) rPDU
The rPDU is a basic socket, rather than a monitoring socket.
Figure 3-3 Half-height rPDU
Table 3-4 rPDU technical specifications
Item
Rated current
Input frequency
Input port
Output port configuration
Rated output current
3.2.5 Lithium Battery ESM-48100B1
Lithium batteries provide backup power. When the mains is normal, the UPS
charges batteries. When the mains fails, lithium batteries supply power to the UPS.
Issue 02 (2020-12-25)
Copyright © Huawei Technologies Co., Ltd.
Specifications
50 Hz/60 Hz
2 x 63 A/2P
63 A/1P
125 A/2P x 2
25 A/1P MCB x 2
63 A/1P
63 A/1P
4 x 40 A/1P
130 mm x 442 mm x 450 mm
Specifications (Vertically Installed
Half-Height rPDU)
32 A
50 Hz/60 Hz
Cord end terminal, no input cable
IEC: 9 x C13 + 3 x C19
China standard: 9 x 10 A + 3 x 16 A
32 A