Figure 6-6 Opening the fuse terminal block
Step 2 Reinstall the fuse terminal block in the power distribution subrack.
Step 3 Close the fuse terminal block.
Step 4 Observe the indicator. If the indicator is on, the fuse is functional.
----End

6.4.2.3 Replacing a UPS2000-G

Prerequisites
● Ensure that the main ground cable of the smart module is securely connected.
● After removing cables, wrap exposed terminals with insulation tape and do not
Step 1 Turn off the battery switch, or remove the wiring terminal between the battery
and the faulty UPS.
Step 2 Turn off the corresponding UPS input and output switches. Use a multimeter to
check whether the UPS input and output terminals and battery terminals are de-
energized.
Step 3 Remove the rear cover from the UPS, and remove the input and output power
cables, battery cable, and signal cable.
Issue 02 (2020-12-25)
Tools: electroprobe, insulation gloves, Phillips screwdriver, multimeter
Materials: A spare UPS of the same model is available and functional.
The UPS is damaged or faulty and cannot work.
NO TICE
block cable labels. If cable labels are blocked, cables may be connected
incorrectly later.
Copyright © Huawei Technologies Co., Ltd.
6 O&M
270