ECC800 Data Center Controller
User Manual
Follow-up Procedure
After the condition for stopping high-density island linkage is met, manually close
the cabinet electronic lock.

6.6.2 FusionModule500/800 Linkage Control

Prerequisites
Linkage Grouping
Table 6-43 FusionModule500/800 linkage grouping
Linkage
Category
Link air
conditioner
fault with
emergency
fan
Issue 04 (2021-10-09)
You have obtained the IP address of the ECC800-Pro as well as the user name
and password used for WebUI login.
A PC with an IP address in the same network segment as that of the ECC800-
Pro is prepared, and the PC has connected to port WAN1 on the ECC800-Pro.
Ensure that Enable linkage control function is Yes.
Default
Status
off
Copyright © Huawei Technologies Co., Ltd.
Function
If this linkage status is set to on:
If all smart cooling products fail to communicate, and
the aisle temperature is higher than 27°C, the
emergency fan starts.
If all smart cooling products fail to provide the cooling
function properly, and the aisle temperature is higher
than 27°C, the emergency fan starts.
6 Feature Description
224