Simodrive 611 series drive converter
Table of Contents

Advertisement

02.12
05.01
HFD reactor con-
nection
HFD reactor
Order No., refer to Table 6-12
Ï Ï
Ï Ï
Cable labeling
Example, 800 W resistor
Cable connection to the resistor.
The cable length of 5 m may be
decreased but not increased.
Connection circuit, 800/1500 W resistor
U/L1/C/L+
1
2
V/L2
3
W/L3/D/L–
PE
PE
1) Jumper, 2–3–PE for potential connection (EMC)
is provided as standard
Note:
It is not permissible to route cables in or close to
the warm airflow of the damping resistor!
Fig. 6-14
Wiring, HFD reactor and damping resistor
© Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
HFD reactor, terminal connection
PE
3
PE
W/L3/D/L–
Shield contact
Ï Ï Ï Ï
Connecting the cable
Ï Ï Ï Ï
to the HFD reactor
Ï Ï Ï Ï
Ï Ï Ï Ï
HFD resistor,
example 800 W
1)
Resistance
6 Infeed Modules
6.5 HFD reactor
1)
2
1
U/L1/C/L+
V/L2
Connection circuit, 300 W resistor
U/L1/C/L+
1
V/L2
2
W/L3/D/L–
3
1)
Resistance
PE
PE
Mounting position:
Arbitrary mounting position but consider the
heat dissipation, if necessary, provide a "Hot
surface" warning notice!