Application Programming; Programming For Controlling Inverter Speed With 5-Step Analog Output Voltage - LG MASTER-K200S Series User Manual

Programmable logic controller
Hide thumbs Also See for MASTER-K200S Series:
Table of Contents

Advertisement

Chapter 8. MK PROGRAMMING

8.2 Application Programming

8.2.1 Programming for Controlling Inverter Speed with 5-step Analog Output Voltage

1) System Configuration
GM4-
K4P -
PA2A
15AS
Input digital value of "0"
Initial
(P0001)
Input digital value of "1000"
(P0002)
Input digital value of "2000"
(P0003)
Input digital value of "3000"
(P0004)
Input digital value of "4000"
(P0005)
2) Initial Settings
(1) Enabled channel : channel 0
3) Descriptions of the Program
(1) P0001 turning On leads to output of "0"(-10 V) on channel 0.
(2) P0002 turning On leads to output of "1000"(-5 V) on channel 0
(3) P0003 turning On leads to output of "2000"(0 V) on channel 0.
(4) P0004 turning On leads to output of "3000"(5 V) on channel 0.
(5) P0005 turning On leads to output of "4000"(10 V) on channel 0.
G4I-
G4F-
D22A
DA3V
8 - 2