58 Technical data
Fuses (option +F260)
ACS880-
7407LC-...
Quantity
0500A-7
1250A-7
3000A-7
Dimensions and weights
ACS880-
7407LC-...
0500A-7
1250A-7
3000A-7
Free space requirements
The values are as required by cooling, maintenance and/or operation of the pressure relief
(if present). Also obey the general mechanical installation instructions.
Front
mm
1500
Losses, internal cooling circuit data and noise
ACS880-
7407LC-...
P
loss total
kW
0500A-7
3.2
1250A-7
7.9
3000A-7
17.9
These losses are not calculated according to IEC 61800-9-2.
Terminal data for the control cables
Nom. voltage / current: 500 V / 17.5 A, connection method: spring-cage connection, cross
section: 0.08 mm² - 1.5 mm² (AWG: 28 - 16)
A
2
800
2
2000
2
5000
Height
Width
mm
2002
2002
2002
in.
mm
59
0
Losses
P
P
loss coolant
loss air
kW
kW
3.0
0.2
7.6
0.3
17.5
0.4
DC fuses
V
1250
Bussmann Eaton
1000
Bussmann Eaton
1000
Bussmann Eaton
Depth
mm
mm
600
644
600
644
600
644
Sides
in.
0
Cooling circuit data
Total
Massflow
l
l/min
5
5.5
6
Manufacturer
Type
170M6546
170M7608
170M7622
Weight
kg
325
378
440
Above
mm
250
9.85
Noise (Avg)
Pressure
loss
kPa
26
120.0
38
120.0
48
120.0
in.
dB(A)
63
63
63