Technical Specifications

6.1

LED feedback

The OccuSwitch DALI provides feedback through different
blinking patterns of the LED indicator .
The following table shows an overview of the possible
LED indications .
Blinking Pattern
Color
Irregular
Red
Irregular
Yellow
Irregular
Green
Cycle
Green –
(0 .5 s per color)
Yellow – Red
Three short blinks
All (Red, Green
(within 0 .5 s)
and Yellow)
Long – short
Yellow –Green
(1 .5 s - 0 .5 s)
Long – short
Red – Green
(1 .5 s - 0 .5 s)
Long – short
Green – Red
(1 .5 s - 0 .5 s)
Continuous color
Red
Continuous color
Yellow
Continuous color
Green
Very fast blinking
Any
Cause
Motion is detected or IR command is received, and the window light output is
above 70% .
Motion is detected or IR command is received, and the window light output is
between 40% and 70% .
Motion is detected or IR command is received, and the window light output is
below 40% .
Walk test mode is activated
A parallel link event is detected during walk test mode .
This only shows once for each parallel link event .
Manual set-point calibration by pushbutton is in progress .
Automatic set-point calibration by pushbutton is in progress .
DALI addressing is activated with an IR remote control .
An external short-circuit is present on one or both DALI outputs,
or the parallel link is not correctly connected,
or there are two OccuSwitch DALI on the same DALI line .
An internal error has occurred .
Burn-in mode is enabled by IR, the window light output has not passed the 100
hours yet and at least one of the light outputs is at 100% .
An infrared interference has occurred . Too many IR remote controls used at the
same time or too much infrared light .
Figure 13: LED indicators of the OccuSwitch DALI