4.3

Reset to factory defaults

The OccuSwitch DALI system can be set to default factory
settings (out of the box settings) using the
IRT9090 .
II
I / II
BMS
PL
W/C
1
2
3
10% A
20% B
30% C
1 Press the Reset button .
4
5
6
40% D
50% E
60% F
7
8
9
The LED on the transmitter starts to
70% G
on
0
o
min
blink .
group
save
2 Point the remote towards the
con g
mode
O)))
OccuSwitch DALI and press the green
link?
mode?
test
100 h
Send button .
add
zone
%
A-G
on/o
0
power up background IR group
reset
The luminaires will flash once to confirm
delay
pir
daylight RF channel
the reset (see also note) .
scene
B Warning
Reset to factory defaults will only reset the
following parameters:
• Application mode (default: 1)
• 100h burn-in mode (default: off)
• Power up state (default: on)
• Background level (default: 20%)
• IR group (default: A)
• DALI groups of all connected luminaires (OccuSwitch
DALI will work in un-commissioned mode)
Depending from which mode the reset to factory is
done and whether there is a parallel linking connection
or not, there are different behaviors after conformation
blinking of lamps . In some modes the lamps stays off
after conformation blink, in other modes the lamps go
back on a few seconds after conformation blinking of
lamps . To make sure that changes are implemented
correctly it is advised to restart the device after a reset
to factory defaults . Please be aware that Groups, that
are created according to chapter 5 .8, are not removed
with this Reset to factory defaults and thus Parallel
Link is not active .
4.4

Walk test

To check that the OccuSwitch DALI system is correctly
installed and commissioned, the OccuSwitch DALI system
can be set into the walk test mode . In this mode, all
actions of the OccuSwitch DALI run at a high speed (10
times faster than normal), movement detection period is
set to 30 seconds (independent of potentiometer settings),
and daylight dependent switching and daylight override
are disabled .
The walk test mode can be started and stopped using the
IRT9090 tool .
II
I/II
Entering the walk test mode
BMS
PL
W/C
1
2
3
10% A
20% B
30% C
4
5
6
40% D
50% E
60% F
7
8
9
1 Point the remote towards the
70% G
on
0
o
min
OccuSwitch DALI and press Test to enter
group
the walk test mode .
save
con g
mode
O )))
The LEDs on the OccuSwitch DALI will start
link?
mode?
test
100 h
running a color sequence .
add
zone
%
A-G
on/o
0
power up background IR group
reset
delay
pir
daylight RF channel
scene
II
I/II
Leaving the walk test mode
BMS
PL
W/C
1
2
3
10% A
20% B
30% C
4
5
6
40% D
50% E
60% F
7
8
9
1 Point the remote towards the
70% G
0
on
o
min
OccuSwitch DALI and press Test to leave
group
the walk test mode .
save
con g
mode
O )))
The luminaires will flash twice to confirm
link?
mode?
test
100 h
the end of walk test mode .
add
zone
%
A-G
on/o
0
power up background IR group
reset
The OccuSwitch DALI returns to normal
delay
pir
daylight RF channel
operation .
scene
D Note
After one hour of being in the walk test mode, the
OccuSwitch DALI will automatically return to normal
operation . In this case it also flashes the luminaires
twice .