2.2.3.1 Long Time Pickup
(Overload Protection setting) Ir
Installed in all Trip Units types the first SETUP
mode display is always the Long Time Pickup
setpoint. This set point establishes the breaker's
ampere rating Ir.
The 1st screen allows the user to define up to 6
different user currents Ie that can be set as a
fraction of 1, 0.98, 0.97, 0.96,0.45 or 0.4 x the
breaker current rating In. These are indicated as
a current value on the screen
The definite current setting Ir is set on the 2nd LT
setting screen as a fraction of the user current
value Ie. (x Ir = LT multiplier x Ie).
There are 11 Long Time Pickup settings ranging
from are 0.50 to 1.00 times x CT in steps of 0.05.
The pickup value is set at a value of
approximately 1.12 x the setting with a
tolerance of -10% to +10%. An additional
accuracy degradation of ±5% occurs when
waveforms with significant harmonic distortion
are present. (For an overview of all available
settings see table 2.4 on page 2-12)
Table 2.3 : Overload Tripping times at indicated overload levels per selected tr band , in Seconds.
Tab. 2.3: Überlast-Auslösezeiten (sec)...
Tabella 2.3: Tempi di intervento per sovraccarico ai livelli di sovraccarico indicati per curva tr selezionata, in secondi.
Thermal Protection type C curves
x Ir
Cmin
C-2
7.8
23.4
Maximum
1.5
4.0
12.0
Minimum
1.3
3.86
Maximum
3
0.80
2.41
Minimum
0.21
0.62
Maximum
7.2
0.13
0.40
Minimum
Motor Protection Class to IEC 947-4
Motorschutz-Klasse nach IEC 947-4
Classe protezione motore a norma IEC 947-4
Fuses or type F curves
x Ir
Fmin
F-2
1.44
4.19
Maximum
1.5
0.64
1.87
Minimum
0.09
0.26
Maximum
3
0.04
0.12
Minimum
Maximum
7.2
Minimum
Standard Inverse curves
x Ir
L-0.5
L-1
1,02
2,05
Maximum
1.5
0,76
1,51
Minimum
0,32
0,64
Maximum
3
0,31
0,63
Minimum
0,18
0,37
Maximum
7.2
Minimum
0,17
0,33
Very Inverse curves
x Ir
L-0.5
L-1
1,69
3,38
Maximum
1.5
1,13
2,25
Minimum
0,36
0,71
Maximum
3
0,64
Minimum
0,32
0,18
0,22
Maximum
7.2
Minimum
0,17
0,21
Extremely Inverse curves
x Ir
L-0.5
L-1
4,23
8,46
Maximum
1.5
2,50
5,00
Minimum
0,56
1,13
Maximum
3
0,44
0,88
Minimum
0,09
0,17
Maximum
7.2
0,07
0,14
Minimum
2.2.3.1 Langzeiteinstellungen
(Überlastschutz Einstellung) Ir
In allen Auslöserarten wurde als erste SETUP-
Modusanzeige immer die Langzeit-Sollwert-
Einstellung installiert. Dieser Sollwert richtet den
Leistungsschalter Stromwert Ir ein.
Das erste Display ermöglicht die Definition, von
bis zu 6 verschiedenen Nutzerströmen Ie, d.h. sie
können als ein Bruchteil von 1, 0,98, 0,97,
0.96,0.45 oder 0,4 x der Schalterstromwerte In
eingegeben werden. Diese werden als
Stromwert auf dem Display angezeigt.
Die definierte Stromeinstellung Ir wird am 2. LT-
Einstellbildschirm als ein Bruchteil des
Stromwerts Ie gesetzt. (x Ir = LT Verstärker xIe).
Es gibt 11 Überlastschutz-Einstellungen im
Bereich von 0,50 bis 1,00 x CT in Schritten von
0,05. Der Spitzenwert ist annähernd der 1,12
fache Einstellwert mit einem Toleranzbereich
von -10% bis +10%. Eine zusätzliche
Herabsetzung der Genauigkeit um ± 5% tritt für
Kurvenformen mit erheblicher harmonischer
Verzerrung ein. (siehe Tab. 2.4 Seite 2-12)
Thermischer Schutz Typ C Kurve
C-3
C-4
C-5
C-6
C-7
C-8
46.7
62.3
93.4
125
156
187
24.0
32.0
48.0
64.1
80.1
96.1
7.73
10.3
15.5
20.6
25.8
30.9
4.82
6.43
9.64
12.9
16.1
19.3
1.24
1.66
2.49
3.32
4.15
4.98
0.81
1.07
1.61
2.15
2.69
3.22
10b
Sicherungen oder Typ F Kurven
F-3
F-4
F-5
F-6
F-7
F-8
7.62
11.9
17.2
23.9
32.3
42.8
3.39
5.30
7.67
10.7
14.4
19.0
0.48
0.74
1.08
1.50
2.01
2.67
0.21
0.33
0.48
0.67
0.90
1.19
0.07
0.08
0.09
0.11
0.01
0.02
0.03
0.04
Standard inverse Kurve
L-2
L-3
L-4
L-5
L-6
L-7
4,09
6,14
8,18 10,23 12,27 14,32 16,36 18,41 20,45 30,68 40,91
3,03
4,54
6,06
7,57
9,09
10,60 12,12 13,63 15,15 22,72 30,30
1,28
1,91
2,55
3,19
3,83
4,47
1,26
1,88
2,51
3,14
3,77
4,40
0,73
1,10
1,47
1,83
2,20
2,56
1,33
0,66
1,00
1,66
1,99
2,33
Erhöht inverse Kurve
L-2
L-3
L-4
L-5
L-6
L-7
6,75
10,13 13,50 16,88
20,25
23,63 27,00 30,38 33,75 50,63 67,50
4,50
6,75
9,00 11,25
13,50
15,75 18,00 20,25 22,50 33,75 45,00
1,42
2,13
2,84
3,55
4,26
4,97
1,29
1,93
2,57
3,21
3,86
4,50
0,44
0,66
0,89
1,11
1,33
1,55
0,43
0,64
0,86
1,07
1,29
1,50
Extrem inverse Kurve
L-2
L-3
L-4
L-5
L-6
L-7
16,92 25,38 33,85 42,31 50,77 59,23 67,69 76,15 84,62 126,9 169,2
10,00 15,00 20,00 25,00 30,00 35,00 40,00 45,00 50,00 75,00 100,0
2,26
3,39
4,52
5,65
6,78
7,91
1,76
2,64
3,52
4,40
5,27
6,15
0,35
0,52
0,70
0,87
1,04
1,22
0,28
0,42
0,56
0,71
0,85
0,99
Protezione termica in curva C
C-9
C-10
C-11
C-12
C-13
C-14
218
249
280
311
374
436
112
128
144
160
192
224
36.1
41.2
46.4
51.5
61.8
72.1
22.5
25.7
28.9
32.1
38.6
45.0
5.81
6.64
7.47
8.30
9.96
11.6
3.76
4.30
4.83
5.37
6.45
7.52
10
20
Fusibili o curva F
F-9
F-10
F-11
F-12
F-13
F-14
56
72
93
118
150
190
25
32
41
53
67
85
3.49
4.51
5.80
7.39
9.39
11.9
1.55
2.01
2.57
3.29
4.18
5.29
0.12
0.14
0.18
0.22
0.28
0.36
0.05
0.06
0.08
0.10
0.13
0.16
Caratteristica inversa standard
L-8
L-9
L-10
L-15
L-20
5,11
5,74
6,38
9,57
12,77
5,02
5,65
6,28
9,42
12,56
2,93
3,30
3,66
5,49
7,33
2,66
2,99
3,32
4,99
6,65
Caratteristica inversa superiore
L-8
L-9
L-10
L-15
L-20
5,68
6,39
7,11
10,66
14,21
5,14
5,79
6,43
9,64
12,86
1,77
1,99
2,21
3,32
4,43
1,71
1,93
2,14
3,21
4,29
Caratteristica inversa estrema
L-8
L-9
L-10
L-15
L-20
9,04
10,17 11,30
16,94
22,59
7,03
7,91
8,79
13,19
17,58
1,39
1,56
1,74
2,61
3,48
1,13
1,27
1,41
2,12
2,82
TRIP UNIT
BREAKER ME10
2.2.3.1 Intervento a lungo ritardo
(Impostazione protezione da sovraccarico) Ir
Installata in tutti i tipi di Relè di Protezione, la
prima modalità di CONFIG visualizzata è sempre
l'impostazione dell'intervento a lungo ritardo.
Questa impostazione stabilisce l'amperaggio Ir
dell'interruttore.
La prima schermata permette all'utente di
definire fino a 6 diverse correnti, le quali possono
essere regolate a 1, 0,98, 0,97, 0,96, 0,45 o 0,4
volte la corrente nominale dell'interruttore In.
Queste sono visualizzate sullo schermo sotto
forma di valore di corrente.
L'impostazione definitiva della corrente Ir
avviene nella seconda schermata di
impostazione LT come frazione del valore della
corrente d'utente Ie. (xLT = moltiplicatore LT x Ie).
Sono previste 11 impostazioni di intervento a
lungo ritardo che vanno da 0,50 a 1,00 x CT, a
passi di 0,05.
Il valore di intervento è fissato a
circa 1,12 x l'impostazione, con una tolleranza
dal -10% al +10%. Un ulteriore riduzione della
precisione del ± 5% si verifica quando sono
presenti forme d'onda con una significativa
distorsione armonica. (Per una panoramica di
tutte le impostazioni disponibili, vedere la tabella
2.4 a pagina 2-12)
minimum = minimo
Maximum = massimo
C-15
C-16
C-17
C-18
C-19
C-20
498
560
623
685
747
810
256
288
320
352
384
416
82.4
92.7
103
113
124
134
51.4
57.8
64.3
70.7
77.1
83.6
13.3
14.9
16.6
18.3
19.9
21.6
8.60
9.67
10.7
11.8
12.9
14.0
30
F-15
F-16
F-17
F-18
F-19
F-20
239
302
380
477
600
752
107
135
169
213
267
335
15.0
18.9
23.8
29.9
37.5
47.0
6.68
8.41
10.6
13.3
16.7
20.9
0.45
0.57
0.72
0.90
1.13
1.42
0.20
0.25
0.32
0.40
0.50
0.63
2
.2
C-21 Cmax
872
934
448
480
144
155
90.0
96.4
23.2
24.9
15.0
16.1
40
F-21 Fmax
942
1153
419
514
58.9
72.1
26.2
32.1
1.78
2.18
0.79
1.03
2-11