Action
Control unit power OFF
then power ON again.
RESET jumper JP4 on the
main board 1556.
Reset command from Win512
or TLON Manager
Automatically due to external
disturbance.
Automatically after download
of site specific data (SSD) via a
PC & Win512.
Operating Instructions Fire alarm system EBL512 V2.3.x

Restart

66
A restart
will delete or not delete the data in the control unit. Here
follow an explanation of the different data, abbreviations and a table
showing how the data respectively is affected.
FFD = Fire alarms, faults and disablements.
SSW =
Week average sensor
calibration values and log buffers.
SSD = Site specific data, i.e. all the installation programming
downloaded from Win512.
SSI = EBL512 settings downloaded from Win512.
S/W = Software, i.e. the control unit system program.
Safe shut down of control unit (menu H8/S8) will save the SSW data
in a Flash ROM before you power off the control unit. Before the first
"Safe shut down" this memory is empty. After each "Safe shut down"
is the latest SSW data saved. When the power supply returns the
control unit RAM (working memory) will, after the restart, read the
SSW data saved in the Flash ROM.
68
and
69
NOTE! During restart, the following will happen:
-- The Fault tx output will be "activated".
-- Outputs S0-S3 programmed as normally high will be low for a few
seconds
66
Restart affects the control unit where it is performed and that control unit's
data in a system.
67
If this memory is empty when the power supply returns, new week
average sensor values will be calculated within two minutes. During the two
minutes all fire alarms from analog smoke detectors will be suppressed.
68
See "Safe shut down of control unit" above.
69
If this happens often, call for service personnel / engineer.
69
values, access codes, supervised output
(Alarm counter when applicable.)
67
Data, etc. which
will be deleted
68
SSW
FFD
FFD
FFD
FFD
FFD
Data, etc. which
will be not deleted
SSD, SSI,
S/W
SSD, SSI,
S/W, SSW
SSD, SSI,
S/W, SSW
SSD, SSI,
S/W, SSW
SSD, SSI,
S/W, SSW