Control Supply Module (CSM)
9.8 Technical data
6SL3100-1DE22-0AA1
Fuses (UL)
1)
UL listed JDDZ: Class RK1, J, CC, CF
IEC: 3NA3801, 3NC1006, 3NW6001
Miniature circuit breaker
IEC: 5SY7306-7
Ambient temperature
Cooling method
Ventilation clearances
above/below
Weight
When using circuit breakers for protection, UL approval is only possible in TN/TT line systems with grounded neutral point.
1)
Conventional fuses are required for UL approval in line supplies with grounded line conductor.
The specified circuit breakers are permissible for UL and IEC.
For applications according to IEC, equivalent circuit breakers and fuses are permissible.
9.8.2

Characteristics

Output current derating
For output voltages > 26 V, the output current must be linearly derated from 20 A @ 26 V to
18 A @ 28.8 V. The maximum output power must not exceed 520 W.
Figure 9-6
Derating of the output current as a function of the installation altitude
Derating is not required up to an installation altitude of 2000 m
Above an installation altitude of 2000 m, a linear derating of 10 % per 1000 meters is required.
144
[A]
20
19,5
19
18,5
18
24
25
26
27
Output voltage U
Current derating for output voltages > 26 V
Unit
Value
A
6 (≥ 480 V
A
6
A
6
°C
0 ... 55
Internal air cooling
mm
≥ 80
kg
4.8
28
29
[V]
out
)
AC
High Frequency Drive
System Manual, 10/2020, 6SL3097-5AH10-0BP0