Definition of Combining Function
Figure 53 shows an example of schedule based on the loop shown in Figure 52.
Figure 52 Example of Loop Connecting Function Block of FVP110 with Other Instruments
Figure 53 Function Block Schedule and Communication Schedule
For the case where the control period (macrocycle) is set to four seconds or longer, set
the following interval larger than 1% of the macrocycle:
The interval between the end of block execution and the start of releasing CD
from LAS.
The interval between the end of a block execution and the start of the next block
execution.