Technical Data - Siemens Sinamics S120 Manual

Liquid-cooled chassis power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

3.3.6

Technical data

Table 3- 13
Technical data for Active Interface Modules, 380 V ... 480 V 3 AC
Article number
Suitable for Active Line Module
Rated power of
Active Line Module
Rated current
Supply voltages
- Line voltage
- Line frequency
- Electronics power supply
- Fan supply voltage
DC-link capacitance
of the drive line-up, max.
Current consumption
- Electronics current consumption (24 V DC)
- Fan supply, 230 V 2 AC, 50/60 Hz, max.
- Max. pre-charging current (max. 3 s)
Bypass contactor
Power consumption bypass contactor
(230 VAC)
- Making current
- Holding current
Max. ambient temperature
- Without derating
- With derating
Power loss, max.
1)
- at 50 Hz 400 V
- at 60 Hz 460 V
Cooling air requirement
Sound pressure level
L
(1 m) at 50/60 Hz
pA
Line/load connection
L1, L2, L3 / U2, V2, W2
PE connection
Max. connection cross-section
- Line connection (L1, L2, L3)
- Load connection (U2, V2, W2)
- PE connection
Degree of protection
Dimensions
- Width
- Height
- Depth
Frame size
Weight
The specified power loss is the maximum value at 100% capacity utilization. The value in normal operation is lower.
1)
Liquid-cooled chassis power units
Manual, (GH7), 11/2016, 6SL3097-4AM00-0BP7
6SL3300–
7TE35–0AA1
6SL3335-
7TE35-0AA3
kW
300
A
490
V
3 AC 380 -10% (-15% < 1 min) ... 3 AC 480 +10%
ACrms
Hz
V
DC
V
AC
µF
76800
A
0.17
A
0.9 / 1.2
A
57
included
A
2.5
A
1.2
° C
40
° C
55
kW
3.9
kW
3.9
m
/s
0.47
3
dB(A)
71 / 73
M10
M10 screw
mm²
2 x 185
mm²
2 x 185
mm²
2 x 185
IP20
mm
325
mm
1533
mm
542
GI
kg
190
Line-side power components
3.3 Active Interface Modules, air-cooled
47 ... 63 Hz
24 (20.4 ... 28.8)
230 (195.5 ... 264.5)
Flat connection for screw
65

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simanics s120