5.2.15 Overcharge Protection

Possible Causes
Solution
1.
2.

5.2.16 Overdischarge Protection

Possible Cause
The battery capacity is low due to a long-time AC power failure.
Solution
Check the cause of the AC power failure and rectify the fault.

5.2.17 Battery Cell N Fault

Possible Cause
The electrochemical cell is faulty.
Solution
Replace the faulty module.

5.2.18 Discharge Overcurrent Protection

Possible Causes
Issue 04 (2020-02-29)
Check whether the battery is located in the heat dissipation area of other equipment. If so,
isolate the heat source or relocate the battery.
Check whether the discharge time in the high-temperature environment meets
requirements. If not, replace the battery.
The PSU charge voltage is incorrectly set.
The PSU is faulty.
Check whether the equalized and float charge voltages are correctly set (see the appendix
"Technical Specifications"). If not, adjust the settings based on site requirements.
Check whether the PSU output voltage is excessively high. If it is higher than the
configured equalized or float charge voltage and cannot be adjusted, replace the PSU.
The load exceeds the maximum power of the lithium battery.
The load is short-circuited.