Ac Undervoltage; Dc Overvoltage; Dc Undervoltage; Parallel Fail - Huawei DPU40D-N06A3 User Manual

Distributed power system
Hide thumbs Also See for DPU40D-N06A3:
Table of Contents

Advertisement

DPU40D-N06A3, DBU20B-N12A3, and
DBU50B-N12A1 Distributed Power System
User Manual
2.

5.2.3 AC Undervoltage

Possible Causes
Solution
1.
2.

5.2.4 DC Overvoltage

Possible Causes
Solution
1.
2.

5.2.5 DC Undervoltage

Possible Causes
Solution
1.
2.
3.

5.2.6 Parallel Fail

Possible Causes
Issue 04 (2020-02-29)
Check whether the AC overvoltage alarm threshold is correctly set. If not, adjust it based
on site requirements.
The grid power is unstable.
The AC undervoltage alarm threshold is incorrectly set.
Measure the AC input voltage. If the voltage is abnormal, rectify the power grid fault.
Check whether the AC undervoltage alarm threshold is correctly set. If not, adjust it
based on site requirements.
The rectifier is faulty.
The DC overvoltage alarm threshold is incorrectly set.
Check whether the indicator on the rectifier is red. If so, replace the rectifier.
Check whether the DC overvoltage alarm threshold is correctly set. If not, adjust it based
on site requirements.
The battery voltage is below the DC undervoltage alarm threshold.
The DC undervoltage alarm threshold is incorrectly set.
The DC output is short-circuited.
Measure the AC input voltage. If the voltage is abnormal, rectify the power grid fault.
Check whether the DC undervoltage alarm threshold is correctly set. If not, adjust it
based on site requirements.
Remove the load and battery cables one by one and check whether the alarm is cleared.
If so, rectify the short circuit. If the battery fuse is blown or a cable is loosely connected,
check and rectify the fault.
The parallel communications cable between rectifiers is loose.
Copyright © Huawei Technologies Co., Ltd.
5 Maintenance
34