Options
9.7 G60, Terminal Module TM31
Note
Ensuring the function of digital inputs
An open input is interpreted as "low".
Terminal M1 must be connected so that the digital inputs (DI) can function.
This is achieved through one of the following measures:
1. Also route the reference ground of the digital inputs.
2. A jumper to terminal M. (Note: This removes the electrical isolation for these digital
inputs.)
X530: 4 digital inputs
Table 9- 9
Connector
Max. connectable cross-section: 1.5 mm²
DI: digital input; M2: ground reference; M: Electronics ground
1)
Note
Ensuring the function of digital inputs
An open input is interpreted as "low".
To enable the digital inputs (DI) to function, terminal M2 must be connected.
This is achieved through one of the following measures:
1. Also route the reference ground of the digital inputs.
2. A jumper to terminal M. (Note: This removes the electrical isolation for these digital
inputs.)
344
Terminal block X530
Terminal
Designation
1
DI 4
2
DI 5
3
DI 6
4
DI 7
5
M2
6
M
Technical data
1)
Voltage: - 3 ... +30 V
Current consumption typical: 10 mA at 24 V DC
Input delay:
For "0" to "1": Typ. 50 µs max. 100 µs
for "1" to "0": Typ. 130 µs, max. 150 µs
Electrical isolation:
Reference potential is terminal M2
Signal level (incl. ripple)
High level: 15 ... 30 V
Low level: -3 ... +5 V
Equipment Manual, 04/2020, A5E37067587A
Cabinet Modules liquid cooled