Load the setpoint file to be upgraded into the EnerVista 489 Setup
environment as described in Adding Setpoints Files to the Environment
on page 4–24.
In the File pane, select the saved setpoint file.
From the main window menu bar, select the File > Properties menu
item and note the version code of the setpoint file.
If this version (e.g. 4.0X shown below) is different than the Software
Revision code noted in step 2, select a New File Version that matches
the Software Revision code from the pull-down menu.
For example, if the software revision is 3.00 and the current setpoint file revision is
1.50, change the setpoint file revision to "3.0X", as shown below.
Enter any special comments
about the setpoint file here.
When complete, click Convert to convert the setpoint file to the desired
revision.
A dialog box will request confirmation. See Loading Setpoints from a
File on page 4–28 for instructions on loading this setpoint file into the
489.
CHAPTER 4: INTERFACES
Select the desired setpoint version
from this menu. The 3.0x indicates
versions 3.00, 3.01, 3.02, etc.
489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL