GE Multilin 489 Instruction Manual page 189

Generator management relay
Hide thumbs Also See for Multilin 489:
Table of Contents

Advertisement

CHAPTER 5: SETPOINTS
489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL
Courtesy of NationalSwitchgear.com
GE Multilin
1000
900
800
700
600
500
400
300
200
100
90
80
70
60
50
40
30
20
10
9
8
7
6
5
4
3
2
1
1
FIGURE 5–17: Thermal Limits for High Inertial Load
To illustrate the Voltage Dependent Overload Curve feature, the thermal limits shown in
Thermal Limits for High Inertial Load on page 5–79 will be used.
Construct a custom curve for the running overload thermal limit.
If the curve does not extend to the acceleration thermal limits, extend it
such that the curve intersects the acceleration thermal limit curves. (see
the custom curve below).
THERMAL LIMITS
FOR HIGH INERTIAL LOAD
1- Running Overload Thermal Limit
1
2- Acceleration Thermal Limit @ 80%V
3- Acceleration Thermal Limit @ 100%V
4- Locked Rotor Thermal Limit
- Machine Acceleration Curve @ 80% V
6- Machine Acceleration Curve @ 100%V
2
3
4
5
6
MULTIPLES OF FULL LOAD AMPS
489
808826A3.CDR
5–79