3-2. Outdoor Unit

RAV-GM1601AT P
Pressure
switch
TD sensor
Accumulator
(1700cc)
Rotary
compressor
RAV-GM1601AT * P *
(MPa)
Pd
Ps
Standard
2.86
0.85
Cooling
Overload
3.40
0.97
Low load
2.92
0.74
Standard
2.97
0.63
Heating
Overload
3.10
1.12
Low load
2.22
0.26
*
4 poles are provided to this compressor.
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
Ball valve
Outer dia. Ø15.88
Strainer
TS sensor
P
4-way valve
Heat exchanger
Muffler
Ø8, 2 rows, 52 steps
FP1.3 flat fin
Ø25 × L210
Ø25 × L160
Pressure
Pipe surface temperature (°C)
(kg/cm
G)
2
Pd
Ps
(TD)
29.2
8.7
91
34.7
9.9
82
29.8
7.5
66
50.3
6.4
88
30.6
11.4
86
22.6
2.6
84
TŌ sensor
TL sensor
TE
sensor
(TS)
(TC)
(TE)
8
8
39
12
15
54
3
4
47
1
49
3
19
52
16
-18
36
-17
- 24 -
Packed valve
Outer dia. Ø9.52
PMV
(Pulse Motor Valve)
Strainer
Distributor
R32 : 2.4kg
Cooling
Heating
*
Temp
Comp.
Fan
Hz
In
68
HIGH
27/19
67
HIGH
32/23
30
LOW
18/13
68
HIGH
20/-
27
LOW
27/-
81
HIGH
15/-
Out
35/-
46/-
-15/-
7/6
24/18
-15/-