Advertisement

5.5.3.10

X49 terminal block

Table 5- 52
Max. connectable cross-section: 1.5 mm
The terminal strip is coded at terminal 6; please use the corresponding connector from the accessory
pack.
Note
Function of the "LAMPPWR" signal
By connecting a signal lamp, the "LAMPPWR" terminal can be used in large cabinet groups for
signaling the power unit in which a problem exists. Once there is a fault in the respective
power supply unit, a voltage of 24 V DC is output at the output.
Note: During a firmware update, the output alternates between 0 V and 24 V.
5.5.3.11

DRIVE-CLiQ interfaces X400, X401, X402

Table 5- 53
Connector
Blanking plate for DRIVE-CLiQ interfaces (50 pcs.) Article number: 6SL3066-4CA00-0AA0
Air-cooled chassis power units
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3
Terminal strip X49
Connector
Terminal
1
2
3
4
5
6
DRIVE-CLiQ interfaces X400, X401, X402
PIN
Signal name
1
TXP
2
TXN
3
RXP
4
Reserved, do not use
5
Reserved, do not use
6
RXN
7
Reserved, do not use
8
Reserved, do not use
A
+ (24 V)
B
M (0 V)
Function
Technical specifications
LAMPPWR
Supply voltage: 24 V DC
Max. Load current: 100 mA
M
If the power unit has a fault condition, then
voltage is available at the terminals.
NC
Reserved, do not use
NC
Reserved, do not use
NC
Reserved, do not use
NC
Reserved, do not use
2
Line Modules
5.5 Active Line Modules Chassis-2
Technical specifications
Transmit data +
Transmit data -
Receive data +
Receive data -
24 V power supply
Electronics ground
231