Figure 5-25
Removing the connection clip to the basic interference suppression module in the Smart Line Module for frame
size JX
NOTICE
Damage to the device through not removing the connection clip with a non-grounded
line supply
Failure to remove the connection clip to the basic interference suppression module on a
non-grounded line supply (IT system) can cause significant damage to the device.
• With a non-grounded line supply (IT system), remove the connection clip to the basic
Air-cooled chassis power units
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3
interference suppression module.