Installation; Set External Shunt Jumper-Option - GE Integritas 3TL125-SACY-D10Y-P000 Quick Start Manual

Wall mount 3 rectifier battery charger
Table of Contents

Advertisement

Installation

Regulations, standards, site engineering instructions, MOPs, etc. take precedence over these general installation instructions.
Tools required:
Wire cutters and strippers
Cable crimpers
Step 1—Set External Shunt Jumper—0ption
The charger is factory configured for an internal shunt.
Set the Shunt Jumper to External if an external shunt is used.
1. Remove charger rear panel—6 screws: 3 each top and bottom.
2. Move both Shunt Jumpers HDR11 and HDR12
to RMT (External) position—pins 2-3.
3. Replace charger rear panel.
Secure with 6 screws.
Jumpers in External (RMT Positions
4
Torque wrench - 0-65 in-lb (0-10 Nm)
Sockets - 5/16", 7/16, etc.
Integritas Wall Mount Charger - Quick Start Guide
Document 8600092587P r03 2018 August
Screwdrivers - Philips and Flat