Information: Controller - View and Change Parameters and Alarm Severity
View and change system parameters and alarm severity
from the factory defaults via:
A. Front Display
B. LAN port in Local mode via a laptop (web pages)
C. LAN port in Network mode (web pages)
D. Craft Port via laptop and EasyView2 software or HyperTerminal.
EasyView2 (GUI) software can be downloaded from www.gecriticalpower.com.
See Pulsar Plus G3 Controller Product Manual for details.
Information: Controller - LAN Port - Local / Network
The LAN port is be configured as Local or Network -
controller display menu path Configuration > Communication Ports > Network Settings > DHCP > mode CLIENT or SERVER
Local
(Server): LAN connects to a laptop.
Local (Server) is a temporary setting. When configuration is complete, return LAN port to Network (Client) mode.
Network (Client): LAN connects to a network. (Default).
CAUTION: Do not connect LAN port to a network when configured as Local.
See Pulsar Plus G3 Controller Product Manual for details.
Information: Controller Alarm Relay Jumpers
Jumpers are located on the side top of the controller.
Alarm Relay Jumper Factory Defaults are Open On Alarm.
1. Remove Controller - 2 thumb screws.
2. Position jumpers per site engineering instructions
3. Replace controller - secure with 2 thumb screws.
Integritas Wall Mount Charger - Quick Start Guide
Document 8600092587P r04 2019 May
15