GT2507T-W

The GOT rugged model uses the environmental protection sheet (not replaceable) with UV
protection function on the front surface.
Therefore, it is possible to suppress deterioration of the touch panel or the liquid crystal display
panel that may be caused by ultraviolet rays.
Note that if the rugged model is exposed to ultraviolet rays for an extended period of time, the front
surface may turn yellow.
If the rugged model is likely to be exposed to ultraviolet rays for an extended period of time, it is
recommended to use a UV protective sheet (option).
Item
Operating ambient temperature
*1
Storage ambient temperature
Operating ambient humidity
Storage ambient humidity
Vibration resistance
Shock resistance
Operating atmosphere
*2
Operating altitude
Installation location
*3
Overvoltage category
*4
Pollution degree
Cooling method
Grounding
*1 The operating ambient temperature indicates the temperature inside the enclosure of the control panel to which the GOT is installed.
*2 Do not use or store the GOT under the atmospheric pressure higher than that at an altitude of 0 m.
Doing so may cause a malfunction.
Air purging by applying pressure to the control panel may create clearance between the surface sheet and the touch panel. This may
cause the touch panel to be not sensitive enough or the sheet to come off.
*3 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power
distribution network and the machinery within the premises.
Category II applies to equipment that is supplied with power from fixed facilities.
The surge withstand voltage is 2500 V for equipment with ratings up to 300 V.
*4 This indicates the occurrence rate of conductive material in an environment where a device is used. Pollution degree 2 indicates an
environment where only non-conductive pollution occurs normally and a temporary conductivity caused by condensation shall be
expected depending on the conditions.
*5 Communication units and options usable with the rugged model can be used in the environment described in the general specifications
of the rugged model.
However, when a protective cover for oil is mounted on the GOT, the operating ambient temperature must be -20°C to 50°C.
For using peripheral devices to be connected to the GOT, refer to the manual of each device.
CAUTION
*5
Specifications
-20 °C to 65 °C
-30 °C to 75 °C
10% RH to 90% RH, non-condensing
10% RH to 90% RH, non-condensing
IEC 60068-2-6
Under intermittent
vibration
Under continuous
vibration
2
IEC 60068-2-27 (392 m/s
(40 G), 3 times in each X, Y, or Z direction)
No greasy fumes, corrosive gas, flammable gas, excessive conductive dust, and direct sunlight (as well as at storage)
2000 m or less
Inside control panel
II or less
2 or less
Self-cooling
Grounding with a ground resistance of 100 Ω or less by using a ground cable that has a cross-sectional area of 2 mm
more. If impossible, connect the ground cable to the control panel.
Frequency
Acceleration
Half
amplitude
5 Hz to 8.4 Hz
7.0 mm
2
8.4 Hz to 150
19.6m/s
Hz
5 Hz to 8.4 Hz
7.0 mm
2
8.4 Hz to 150
19.6 m/s
Hz
3 SPECIFICATIONS
3.1 General Specifications
3
Sweep
count
X, Y, or Z
10 times in
each Z
direction
2
or
61