Advertisement

About Programming
5.4 International/North American Default
Parameter Settings
Setting K-03 Regional Settings to [0] International or [1]
North America changes the default settings for some
parameters. Table 5.1 lists those parameters that are
effected.
Parameter
5
K-03 Regional
5
Settings
P-07 Motor Power
[kW]
P-02 Motor Power
[HP]
F-05 Motor Rated
Voltage
F-04 Base
Frequency
F-53 Maximum
Reference
F-54 Reference
Function
F-17 Motor Speed
High Limit [RPM]
See Note 3 and 5
F-15 Motor Speed
High Limit [Hz]
See Note 4
F-03 Max Output
Frequency 1
H-73 Warning
Speed High
E-03 Terminal 27
Digital Input
E-24 Function Relay No operation
AN-15 Terminal 53
High Ref./Feedb.
Value
AN-50 Terminal 42
Output
H-04 Auto-Reset
(Times)
Table 5.1 International/North American Default Parameter Settings
Note 1: P-07 Motor Power [kW] is only visible when K-03 Regional
Settings is set to [0] International.
Note 2: P-02 Motor Power [HP], is only visible when K-03 Regional
Settings is set to [1] North America.
5-4
AF-650 GP
International
North American
default parameter
default parameter
value
value
International
North America
See Note 1
See Note 1
See Note 2
See Note 2
230 V/400 V/575 V
208 V/460 V/575 V
50 Hz
60 Hz
50 Hz
60 Hz
Sum
External/Preset
1,500 PM
1,800 RPM
50 Hz
60 Hz
132 Hz
120 Hz
1,500 RPM
1,800 RPM
Coast inverse
External interlock
No alarm
50
60
No operation
Speed 4–20 mA
Manual reset
Infinite auto reset
TM
Design and Installation Guide
Note 3: This parameter is only visible when K-02 Motor Speed Unit is
set to [0] RPM.
Note 4: This parameter is only visible when K-02 Motor Speed Unit is
set to [1] Hz.
Note 5: The default value depends on the number of motor poles. For
a 4-poled motor, the international default value is 1,500 RPM, and
for a 2-poled motor, 3000 RPM. The corresponding values for North
America is 1800 and 3600 RPM, respectively.
5.4.1 Parameter Data Check
1.
Press [Quick Menu].
2.
Scroll to Parameter Data Check and press [OK].
Figure 5.12
3.
Select Parameter Data Check to view all
programming changes or Last 10 Changes for the
most recent.

5.5 Parameter Menu Structure

Establishing the correct programming for applications
often requires setting functions in several related
parameters. These parameter settings provide the
adjustable frequency drive with system details it needs to
operate properly. System details may include such things
as input and output signal types, programming terminals,
minimum and maximum signal ranges, custom displays,
automatic restart, and other features.
See the keypad display to view detailed
parameter programming and setting options.
Press [Info] in any menu location to view
additional details for that function.
Press and hold [Main Menu] to enter a parameter
number for direct access to that parameter
Details for common application set ups are
provided in 6 Application Setup Examples.