Control Terminal Types - GE AF-650 GP Design And Installation Manual

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Installation
Figure 2.17 Control Wiring Access for IP55/ Nema 12 and IP66 /
Nema 4/4X Indoor

2.5.5.2 Control Terminal Types

Figure 2.18 and shows the removable adjustable frequency
drive connectors. Terminal functions and default settings
are summarized in Table 2.4.
Figure 2.18 Control Terminal Locations
Figure 2.19 Terminal Numbers
TM
AF-650 GP
Design and Installation Guide
See 13.2 General Technical Data for terminal ratings details.
Terminal Parameter
12, 13
18
19
32
33
27
29
20
37
39
DET-767A
Connector 1 provides four programmable digital
inputs terminals, two additional digital terminals
programmable as either input or output, a 24 V
DC terminal supply voltage, and a common for
optional customer supplied 24 V DC voltage. A
digital input for STO (Safe Torque Off) function.
Connector 2 terminals (+)68 and (-)69 are for an
RS-485 serial communications connection
Connector 3 provides two analog inputs, one
analog output, 10 V DC supply voltage, and
commons for the inputs and output
Connector 4 is a USB port available for use with
the DCT-10
Also provided are two Form C relay outputs that
are in various locations depending upon the
adjustable frequency drive configuration and size
Some options available for ordering with the unit
may provide additional terminals. See the manual
provided with the equipment option.
Terminal description
Default
setting
Digital inputs/outputs
-
+24 V DC
E-01
[8] Start
E-02
[10] Reversing
E-05
[0] No
operation
E-06
[0] No
operation
E-03
[0] No
operation
E-04
[14] JOG
-
-
Safe Torque
Off (STO)
Analog inputs/outputs
-
2
Description
24 V DC supply
voltage. Maximum
output current is 200
mA total for all 24 V
loads. Usable for
digital inputs and
external transducers.
Digital inputs.
Selectable for either
digital input or
output. Default setting
is input.
Common for digital
inputs and 0 V
potential for 24 V
supply.
Safe input. Used for
STO.
Common for analog
output
2-11
2

Advertisement

Table of Contents
loading