b) (02311FTC-004 and 02311FTE-004 cabinets) Set ATS parameters.
c) After you perform the settings, the Bypass mode and No battery alarms are reported by the
MDU and do not need to be cleared. If there is any other alarm, you need to rectify the fault.
d) On the monitoring screen, tap the UPS icon to verify that the UPS is working in bypass mode.
e) Start the inverter on the app.
•
The Service Expert app can be downloaded from Huawei app store and can run on Android.
•
The port number is 443 by default and can be modified. If the UPS is managed using the app,
the port number must be set to 443.