Huawei UPS5000-E Series Quick Manual page 14

Integrated ups 3.0
Hide thumbs Also See for UPS5000-E Series:
Table of Contents

Advertisement

Number of
Battery
Batteries
Specifications
Connected in
Series
100 Ah/12 V
32
192
100 Ah/2 V
40
100 Ah/12 V
100 Ah/2 V
240
Number of cells indicates the number of 2 V DC batteries in a battery string connected to the
UPS.
If multiple UPSs share battery strings, the battery capacity of each UPS is the total capacity of the
battery strings.
Number of Battery
Strings Connected
in Parallel to the
UPS
2
2
3
4
14
Number of
Battery Capacity
Cells
100 Ah + 100 Ah = 200
32 x 6 = 192
Ah
100 Ah + 100 Ah = 200
192 x 1 = 192
Ah
100 Ah + 100 Ah + 100
40 x 6 = 240
Ah = 300 Ah
100 Ah + 100 Ah + 100
240 x 1 = 240
Ah + 100 Ah = 400 Ah

Advertisement

Table of Contents
loading

Table of Contents