Toshiba MMD-AP0481HF2UL Service Manual page 48

Multi type air-conditioner
Hide thumbs Also See for MMD-AP0481HF2UL:
Table of Contents

Advertisement

< Based on the SMMS-e >
CODE No.
00
Room temperature(Use to control)
01
Room temperature(Remote control)
02
Indoor suction air temperature (TA)*
03
Indoor coil temperature (TCJ)*
04
Indoor coil temperature (TC2)*
05
Indoor coil temperature (TC1)*
06
Indoor discharge air temperature (TF)*
08
Indoor PMV opening
F3
Filter sign time
0A
No. of connected indoor units
0B
Total capacity of connected indoor units
0C
No. of connected outdoor units
0D
Total capacity of connected outdoor units
CODE No.
U1
U2
U3
10
20
30
High-pressure sensor detention pressure (Pd)
11
21
31
Low-pressure sensor detention pressure (Ps)
12
22
32
Compressor 1 discharge temperature (TD1)
13
23
33
Compressor 2 discharge temperature (TD2)
15
25
35
Outdoor coil temperature (TE1)
16
26
36
Outdoor coil temperature (TE2)
17
27
37
Outdoor coil temperature (TG1)
18
28
38
Outdoor coil temperature (TG2)
19
29
39
Outside ambient temperature (TO)
1A
2A
3A
Suction temperature (TS1)
1C
2C
3C
Suction temperature (TS3)
1D
2D
3D
Temperature at liquid side (TL1)
1E
2E
3E
Temperature at liquid side (TL2)
1F
2F
3F
Temperature at liquid side (TL3)
CODE No.
U1
U2
U3
50
60
70
PMV1 opening
51
61
71
PMV3 opening
52
62
72
PMV4 opening
1 fan model : Compressor 1 curent (I1)
53 63 73
2 fan model : Compressor 1 and Outdoor fan 1 current (I1)
1 fan model : Compressor 2 and Outdoor fan 1 current (I2)
54 64 74
2 fan model : Compressor 2 and Outdoor fan 2 current (I2)
56
66
76
Compressor 1 revolutions
57
67
77
Compressor 2 revolutions
59
69
79
Outdoor fan mode
5A
6A
7A
Compressor IPDU 1 heat sink temperature
5B
6B
7B
Compressor IPDU 2 heat sink temperature
5D
6D
7D
Outdoor fan IPDU 1 heat sink temperature
5E
6E
7E
Outdoor fan IPDU 2 heat sink temperature
5F
6F
7F
Outdoor unit capacity
90
Heating/cooling recovery controlled
91
Pressure release
92
Pressure release
93
Follower unit release (U2/U3 outdoor units)
*1 The Outside Air Unit uses the revised sensor data, therefore the data below are not correctly displayed
because they are revised sensor data.
Indoor suction air temperature (TA)
Indoor coil temperature (TCJ)
Indoor coil temperature (TC2)
Indoor coil temperature (TC1)
*2 Only a part of indoor unit types is installed with the discharge air temperature sensor. This temperature is
not displayed for other types.
*3 When the units are connected to a group, data of the header indoor unit only can be displayed.
*4 The indications, U1, U2, U3 indicate the following outdoor units, respectively. For the indication data of each
outdoor unit, check CODE No.
U1...outdoor unit (Header unit)
U2...outdoor unit (Follower unit 1)
U3...outdoor unit (Follower unit 2)
Data name
1
1
1
1
2
Data name
Data name
Display format
Unit
×1
°C
×1
°C
×1
°F
×1
°F
×1
°F
×1
°F
°F
×1
×1/10
pls
×1
h
×1
unit
×10
ton
×1
unit
×10
ton
Display format
Unit
×10
psi
×10
psi
×1
°F
×1
°F
×1
°F
×1
°F
×1
°F
×1
°F
×1
°F
×1
°F
×1
°F
×1
°F
×1
°F
×1
°F
Display format
Unit
×1
pls
×1
pls
×1
pls
×10
A
×10
A
×10
rps
×10
rps
×1
mode
×1
°F
×1
°F
×1
°F
×1
°F
×10
ton
0:Normal
0:Normal
1:Release controlled
– 48 –
Remote control display example
[0027] = 27°C
[0080] = 80°F
[0150] = 1500pls
[2500] = 2500h
[0048] = 48units
[0215] = 21.5ton
[0003] = 3units
[0160] = 16ton
Remote control display example
[4350] = 435 psi
[0080]= 80 °F
Remote control display example
[0500] = 500pls
[0135] = 13.5A
[0642] = 64.2rps
[0058] = 58 mode
[0024] = 24 oF
[0080] = 8 ton
[0010]=Heating recovery controlled
[0010]=Pressure release controlled
[0001]=Discharge temperature release controlled
[0100]=U2 outdoor unit release controlled