Toshiba MMD-AP0481HF2UL Service Manual page 108

Multi type air-conditioner
Hide thumbs Also See for MMD-AP0481HF2UL:
Table of Contents

Advertisement

Table
CODE No. table (Please record the objective unit data at field)
DN
01
Filter sign lighting time
02
Dirty state of filter
03
Central control address
06
Heating suction temp shift
0C
PRE-DEF indication selection
0F
Cooling only
10
Type
11
Indoor unit capacity (See below table)
12
Refrigerant line address
13
Indoor unit address
14
Group adress
28
Automatic restart from power cut
2A
Option input selection (CN080)
2b
Thermo output selection (T10)
2E
HA terminal (T10) selection
32
Sensor selection
60
Timer set (Wired remote control)
72
Fan OFF in defrosting time
Type (CODE No. [10])
Setup data
0001*
0016
Indoor unit capacity (CODE No.[11])
Setup data
Model
0001*
Invalid
0017
048 type
0021
072 type
0023
096 type
* Initial value EEPROM installed on supplied service P.C. board.
Item
Type
Invalid
Outside Air Unit
Memo
Model abb. name
∗∗∗
MMD-AP
HF2UL
– 108 –
At shipment
0002: 2500 hour
0000: Standard
0099: Unfixed
0002: +3.6˚F (+2˚C)
0000: Standard
0000: Heat pump
According to model type
According to capacity type
0099: Unfixed
0099: Unfixed
0099: Unfixed
0001: Available
0002: External emergency input
0000: Thermo ON
0000: Available (HA terminal)
0000: Available
0000: Available
0001: To OFF