Hydran* 201i Instruction Manual
CAUTION
6. Inspect the adaptor and sensor for oil leaks.
7. Dispose of the collected oil according to company standards.
7.3.7 Fastening the Hydran 201Ti to the Brass Adapter
1. Using the supplied 3/16-in Allen key, fasten the H201Ti's heating plate to the
brass adaptor with the six 1/4-28 cap screws. See Figure 7-8 below.
CAUTION
MA-033
Rev. 14.0, 12-Nov-18
Do not use any solvent.
Figure 7-7: Purging Air from the Hydran 201 Sensor
Be careful not to squeeze the nearby electrical wires between
the lock washers and the heating plate or not to damage the
supervisory link (and analog output) termination board.
Page 111