Additional system components
9.1 Terminal Module TM54F
Note
The operating ranges of the F-DI meet the requirements of EN 61131-2 for Type 1 digital
inputs.
The rated values of the F-DO meet the requirements of EN 61131-2 for digital DC outputs
with 0.5 A rated current.
Note
For cable lengths > 30 m, shielded cables must be used for the F-DI.
9.1.2
Safety instructions for TM54F Terminal Modules
Fire through overheating due to insufficient ventilation clearances
Inadequate ventilation clearances can cause overheating with a risk for personnel due to
smoke and fire. This can also result in increased failure rates and a shorter service life for
Terminal Modules.
• It is absolutely essential that you maintain ventilation clearances according to the table
NOTICE
Damage through use of incorrect DRIVE-CLiQ cables
Damage or malfunctions can occur on the devices or the system when incorrect or
unreleased DRIVE-CLiQ cables are used.
• Only use suitable DRIVE-CLiQ cables that have been released by Siemens for the
Note
Malfunctions due to soiled DRIVE-CLiQ interfaces
Malfunctions can occur in the system through the use of soiled DRIVE-CLiQ interfaces.
• Cover unused DRIVE-CLiQ interfaces with the supplied blanking covers.
190
WARNING
Ventilation clearances above and below the component (Page 294).
respective application.
SINAMICS S120 Combi
Manual, 11/2017, 6SL3097-4AV00-0BP7