Toshiba OIS PLUS Series User Manual

Toshiba OIS PLUS Series User Manual

Programmable logic controllers operator interface stations
Hide thumbs Also See for OIS PLUS Series:
Table of Contents

Advertisement

UM-OISPLUS-E001
Programmable Logic Controllers
USER'S MANUAL
Hardware & Specifications
CONTENTS
OIS PLUS
Operator Interface Stations
Toshiba International Corporation
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba OIS PLUS Series

  • Page 1 UM-OISPLUS-E001 Programmable Logic Controllers USER’S MANUAL Hardware & Specifications CONTENTS OIS PLUS Operator Interface Stations Toshiba International Corporation Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 2 Thank you for purchasing the OIS PLUS (Operator Interface Stations) product from Toshiba International Corp. OIS PLUS Series products are versatile industrial displays which are configured with Microsoft Windows based software. Manual’s Purpose and Scope This manual provides information on how to safely install, operate, and maintain your TIC OIS PLUS.
  • Page 3 The sales contract contains the entire obligation of Toshiba International Corporation. The warranty contained in the contract between the parties is the sole warranty of Toshiba International Corporation and any statements contained herein do not create new warranties or modify the existing warranty.
  • Page 4 Manual Revisions Please have the following information available when contacting Toshiba International Corp. about this manual. OIS PLUS User’s Manual: Hardware & Specifications Name: Document: UM-OISPLUS-E001 Revision: Rev No. Date Description 2012/02/14 Initial Issue (for OIS PLUS) Related Manuals UM-OISPLUS-E002: Display Programming...
  • Page 5: Table Of Contents

    INTRODUCTION ..............................12 1.1 Purpose of this Manual ..........................13 1.1.1 OIS PLUS Basics ..........................13 1.1.2 Hardware Requirements ........................13 1.2.1 OIS PLUS Series Overview ........................15 1.2.2 How the OIS PLUS Works ........................16 HARDWARE ...............................19 2.1 OIS PLUS Models .............................20 2.2 OIS PLUS Feature Matix (based on product codes) ..................22 2.3 OIS PLUS Feature Matrix ..........................23...
  • Page 6 2.5.5 TRPDOX0016.............................47 2.5.6 TRPAIO202L (2 AI, 2 AO) ........................49 2.5.7 TRPAIO0400L (4 AI) ...........................51 2.5.8 TRPAIO0402U-16 (4 AI, 2 AO)......................53 2.6 Installation Instructions..........................57 2.6.1 Panel Cut-out and Mounting for OIS45 & 55 PLUS Models ..............57 2.6.2 Panel Cut-out and Mounting for OIS60 & 70 PLUS Models ..............59 2.6.3 Panel Cut-out and Mounting for OIS10 &...
  • Page 7 USB HOST OPERATION ............................. 104 7.1 Overview .............................. 106 7.2 Downloading from USB Drive to OIS PLUS: ....................107 7.3 Uploading from OIS PLUS to USB Drive: ....................109 USB UPLOAD AND DOWNLOAD ........................111 8.1 Upload ..............................112 8.2 Download ............................. 114 8.3 Device Information..........................
  • Page 8 0. General Safety Instructions and Information • Warning Labels Within Manual • Equipment Warning Labels • Preparation Installation Precautions • • Connection, Protection & Setup • System Integration Precautions • 3rd Party Safety Certifications Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 9: Warning Labels Within Manual

    0.1 Warning Labels Within Manual DO NOT attempt to install, operate, maintain, or dispose of this equipment until you have read and understood all of the product warnings and user directions that are contained in this instruction manual. Listed below are the signal words that are used throughout this manual followed by their descriptions and associated symbols.
  • Page 10 To identify special hazards, other symbols may appear in conjunction with the DANGER, WARNING, and CAUTION symbols. These warnings describe areas that require special care and/or strict adherence to the procedures to prevent serious injury and possible death. Electrical Hazard — The electrical hazard symbol is a lightning bolt enclosed in a triangle. The electrical hazard symbol is used to indicate high voltage locations and conditions that may cause serious injury or death if the proper precautions are not observed.
  • Page 11: Equipment Warning Labels

    DO NOT remove or cover any of the labels. If the labels are damaged or if additional labels are required, contact your Toshiba representative for additional labels. The following are examples of the warning labels that may be found on the equipment and...
  • Page 12: Preparation

    • Check to see that the model number specified on the nameplate conforms to the order specifications. • Modification of this equipment is dangerous and must not be performed except by factory trained representatives. When modifications are required contact your Toshiba representative. • Inspections may be required before and after moving installed equipment.
  • Page 13: Installation Precautions

    Handling and Storage • Use proper lifting techniques when moving the OIS; including properly sizing up the load, and getting assistance if required. • Store in a well-ventilated covered location and preferably in the original carton if the equipment will not be used upon receipt. •...
  • Page 14 Conductor Routing and Grounding • Use separate metal conduits for routing the input power, and control circuits. • A separate ground cable should be run inside the conduit with the input power, and control circuits. • DO NOT connect control terminal strip return marked CC to earth ground. •...
  • Page 15: Connection, Protection & Setup

    0.5 Connection, Protection & Setup Personnel Protection • Installation, operation, and maintenance shall be performed by Qualified Personnel Only. • A thorough understanding of the OIS will be required before the installation, operation, or maintenance of the OIS. • Rotating machinery and live conductors can be hazardous and shall not come into contact with humans.
  • Page 16 The failure of external or ancillary components may cause intermittent system operation, i.e., the system may start a motor without warning or may not stop on command. • There may be thermal or physical properties, or ancillary devices integrated into the overall system that may allow the OIS to start a motor without warning.
  • Page 17: System Integration Precautions

    The following precautions are provided as general guidelines for using an OIS in an industrial or process control system. • The Toshiba PLC is a general-purpose product. It is a system component and is used in conjunction with other items of industrial equipment such as PLCs, Loop Controllers, Adjustable Speed Drives, etc.
  • Page 18: Rd Party Safety Certifications

    0.7 3 Party Safety Certifications. CE Marking The V200 Series Programmable Controllers conform to the directive and standards of ISO/IEC Guide 22 and EN 45014. UL Certification The UL Mark on a product means that UL has tested and evaluated representative samples of that product and determined that they meet UL requirements.
  • Page 19: Introduction

    INTRODUCTION ♦ Purpose of this Manual OIS PLUS Basics Hardware Configuration ♦ OIS PLUS Overview ♦ What is an OIS PLUS ♦ How does the OIS PLUS Work? Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 20: Purpose Of This Manual

    Microsoft® Windows based configuration Software. This Manual explains the operation of the OIS PLUS Series and how to implement available features using the OIL-DS Configuration Software. This manual will help you to install, configure and operate your OIS PLUS product.
  • Page 21 Minimal PC configuration for Vista/Win7: DEVICE RECOMMENDED Processor 1GHz Pentium processor or equivalent processor Operating System Microsoft Windows Vista Home and Vista Business edition Hard Disk Space 800MB (including 200MB for the .NET Framework Redistributable) Display 1024 x 768 High Color 16-bit Mouse/Keyboard Required These are the minimum system requirements for a computer running the OIL-DS Configuration software.
  • Page 22: Ois Plus Series Overview

    1.2.1 OIS PLUS Series Overview OIS PLUS product line provides Human-Machine Interface to the Programmable Logic Controller. These OIS PLUSs communicate with PLCs using their serial communications ports. Configuration of OIS PLUS unit: Each OIS PLUS unit has to be configured using the OIL-DS Configuration Software before connecting it to the PLC.
  • Page 23: How The Ois Plus Works

    1.2.2 How the OIS PLUS Works The OIS PLUS follows a specific sequence for performing the tasks defined by the user in the application. The sequence is as shown below: Start Initialize Screens. Initialize Hardware Peripherals. Check if Wait to download application Application present? Restart...
  • Page 24 Request Complete IBM Communication for IBM Comm? Restart Fill Alarm Container If RTC If any groups defined for logging changed then lock the data by 1 sec Global Task f New screen? Upload Block list After Hiding task (Last screen) Before showing task Display / Print screen Display Associated screen...
  • Page 25 While showing task for Popup screen Check Press? Serve Key task Check Reestablish PLC Communication co m m error? Flush SPI FIFO Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 26: Hardware

    HARDWARE ♦ OIS PLUS Models OIS PLUS Models Comparison between OIS PLUS Models ♦ Installation Instructions Panel cut-out for OIS PLUS Models Wiring Diagrams Communication Ports Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 27: Ois Plus Models

    2.1 OIS PLUS Models OIS PLUS series models are Human Machine Interfaces. OIS PLUS models need +24VDC power from an external supply. OIS PLUSs are divided into 2 (two) parts as base models and clip-on I/O models. Base Models included in the OIS PLUS Series are as follows:...
  • Page 28 Clip-on I/O Models are also divided into two parts as: Digital and analog models Digital Clip-on I/O Models: TRPDIX1600 16 Digital Inputs (sinking or sourcing) TRPDOX0016P 16 PNP transistor outputs (Rating: 0.5A) TRPDOX0016N 16 NPN transistor outputs (Rating: 0.5A) TRPRO0012R 12 relays (5A per common) outputs (Relay rating: 2Amp) TRPDIO0808P 8 Digital inputs (PNP or NPN) and 8 PNP transistor outputs (Rating: 0.5A)
  • Page 29: Ois Plus Feature Matix (Based On Product Codes)

    2.2 OIS PLUS Feature Matix (based on product codes) Ethernet Model Display Local I/O Expansion ports OIS10 PLUS 2x16 T ext 8 DC in Device Multi color 6 Relays 2A backlit 2 NPN 0.5A OIS12 2x16 T ext Device Multi color backlit OIS20 PLUS 128x64 Mono...
  • Page 30: Ois Plus Feature Matrix

    2.3 OIS PLUS Feature Matrix Based on other specifications Application Logging Serial Model Display Keys Memory Ladder Steps memory ports OIS10 PLUS 2x16 T ext 18 keys 512K 10K Steps N.A. RS232/485 Multicolor backlit OIS12 2x16 T ext 18 keys 512K 10K Steps N.A.
  • Page 31: Ois Plus Specifications

    2.4 OIS PLUS Specifications 2.4.1 OIS10 PLUS Miscellaneous Power Supply 24 VDC External Dimension 109 H X 71 W X 35 D mm Voltage Rating 24 VDC +/-15% Panel Cutout 99.00 mm x 63.00 mm Power Rating 2 Watt Weight 220 gm.
  • Page 32 Local I/O Specifications for OIS10 PLUS Digital Inputs 8 Normal inputs Bidirectional type. Digital outputs 6 Relay outputs, 2 PWM / Normal outputs Rated Input voltage Rated Input Current Input Impedance Minimum ON voltage Maximum OFF voltage Turn ON time 10 msec Turn OFF time 10 msec...
  • Page 33: Ois12

    2.4.2 OIS12 Miscallaneous Power Supply 24 VDC External Dimension 109 H X 71 W X 35 D mm Voltage Rating 24 VDC +/-15% Panel Cutout 99.00 mm x 63.00 mm Power Rating 2 Watt Weight 172 gm. Approvals CE, UL, RoHS Ambient Operating C to 50 C Temperature...
  • Page 34: Ois40 Plus

    2.4.3 OIS40 PLUS Miscallaneous Power Supply 24 VDC External Dimension 109 H X 71 W X 35 D mm Voltage Rating 24 VDC +/-15% Panel Cutout 99.00 mm x 63.00 mm Power Rating 5 Watt Weight 156 gm. Approvals CE, UL, RoHS Ambient Operating C to 50 C Temperature...
  • Page 35: Ois20 Plus

    2.4.4 OIS20 PLUS Miscallaneous Power Supply 24 VDC External Dimension 128 H X 102 W X 45 D mm Voltage Rating 24 VDC +/-15% Panel Cutout 119.00 mm x 93.00 mm Power Rating 3 Watt Weight 320 gm. Approvals CE, UL, RoHS Ambient Operating C to 50 C Temperature...
  • Page 36 LOAD LOAD Local I/O Specifications of OIS20 PLUS LOAD Digital Inputs 12 Normal inputs Bidirectional type. Digital outputs 6 Relay outputs, 2 PWM / Normal outputs Rated Input voltage Rated Input Current Input Impedance Minimum ON voltage Maximum OFF voltage Turn ON time 10 msec Turn OFF time...
  • Page 37: Ois22 Plus

    2.4.5 OIS22 PLUS Miscallaneous Power Supply 24 VDC External Dimension 128 H X 102 W X 45 D mm Voltage Rating 24 VDC +/-15% Panel Cutout 119.00 mm x 93.00 mm Power Rating 3 Watt Weight 265 gm. Approvals CE, UL, RoHS Ambient Operating C to 50 C Temperature...
  • Page 38: Ois55 Plus

    2.4.6 OIS55 PLUS Miscallaneous Power Supply 24 VDC External Dimension 128 H X 102 W X 45 D mm Voltage Rating 24 VDC +/-15% Panel Cutout 119.00 mm x 93.00 mm Power Rating 4 Watt Weight 285 gm. Approvals CE, UL, RoHS Ambient Operating C to 50 C Temperature...
  • Page 39: Ois45E Plus

    2.4.7 OIS45E PLUS Miscallaneous Power Supply 24 VDC External Dimension 128 H X 102 W X 45 D mm Voltage Rating 24 VDC +/-15% Panel Cutout 119.00 mm x 93.00 mm Power Rating 6 Watt Weight 330 gm. Approvals CE, UL, RoHS Ambient Operating C to 50 C Temperature...
  • Page 40 Counter Coils 256 points Display Display Size & Type 4.3” WQVGA TFT Color Display Display Resolution 480 X 272 Pixels Touch Screen Analog Resistive Communications 2 COMP Ports Port 1: RS232 and 1 RS485/422 2 USB Ports 1 USB Device and 1 USB Host Ethernet Port 1 Ethernet Port Expansion Port...
  • Page 41: Ois60 Plus

    2.4.8 OIS60 PLUS Communication Power Supply 24 VDC 2 COM Ports COM1: RS232/485/422 Voltage Rating 24 VDC +/-15% COM2: RS232/485/422 Power Rating 10 Watt 2 USB Ports 1 USB Device and 1 USB Host Approvals CE, UL, RoHS Expansion Port Miscallaneous Bezel IP65 Rated...
  • Page 42: Ois70E Plus

    2.4.9 OIS70E PLUS Power Supply 24 VDC Communication Voltage Rating 24 VDC +/-15% 2 COM Ports COM1: RS232/485/422 COM2: RS232/485/422 Power Rating 9 Watt 2 USB Ports 1 USB Device and 1 USB Host Approvals CE, UL, RoHS Ethernet Port 1 Ethernet Port Bezel IP66 Rated...
  • Page 43: Ois120A

    2.4.10 OIS120A Communication Power Supply 24 VDC 2 COM Ports COM1: RS232/485/422 Voltage Rating 24 VDC +/-15% COM2: RS232/485/422 Power Rating 12 Watt 2 USB Ports 1 USB Device and 1 USB Host Approvals CE, RoHS Ethernet Port 1 Ethernet Port Expansion Port None Bezel...
  • Page 44: Ois Plus Clip-On I/O Models

    2.5 OIS PLUS Clip-on I/O Models Certain displays in the OIS PLUS accept Clip-on I/O modules. Specifications for these modules follow: 2.5.1 TRPDIO0808 (8 inputs, 8 outputs) TRPDIO0808P = (PNP Type transistor output) TRPDIO0808N = (NPN Type transistor output) Power 3.9VDC, 0.3W from FP base model Approvals CE, UL...
  • Page 45 GDD288P*S Wiring diagram of (PNP Type transistor output): 1. Wiring diagram for testing digital inputs: PED0808P H/W Rev. A5 LISTED 4 9 RN CO M S u rro u n d i n g Ai r T emp eratu re T a= Max. 50 IP COM RENU ELECTR O NI CS Survey No.
  • Page 46 Wiring diagram of TDRDIO0808N (NPN Type transistor output): 1. Wiring diagram for testing digital inputs: PED0808N H/W Rev . A5 LISTED 4 9 RN CO M S u rro u n d i n g Ai r T emp eratu re T a= Max. 50 IP COM RENU ELECTR O NI CS Survey No.
  • Page 47: Trphio0808 (8 Inputs, 8 Outputs, High Speed)

    2.5.2 TRPHIO0808 (8 inputs, 8 outputs, high speed) TRPHIO0808N = (NPN Type transistor output) TRPHIO0808N = (PNP Type transistor output) 24V DC Digital Inputs Number of Inputs 8 Inputs Bi-directional Type (Within which 4 are high speed) Input Design According to EN 61131-2 Type 1 Minimum ON Voltage 15 VDC Maximum ON Voltage...
  • Page 48 High Speed Counter Features Up Counter Single Number of channels 4 ( X0, X5, X2, X7) Phase Physical reset input X1, X6, X3, X4 Maximum input frequency (per channel) 25KHz Input count register (per channel) 1 (32-bit) Preset registers (per channel) 1 (32-bit) Configurable forced output 4 (Y1, Y6, Y7, Y0)
  • Page 49 Wiring diagram of TRPHIO0808N and TRPHIO0808P: 1. High Speed Counter Input Connection (Sink): 2. High Speed Counter Input Connection (Source) PED0808N PED0808N H/W Rev . A5 H/W Rev. A5 LISTED LISTED 4 9 RN 4 9 RN Sur r oundi n g Ai r Sur r oundi n g Ai r Tem per at ur e...
  • Page 50: Trpdix1600 (16 Channel Bidirectional Inputs Only)

    2.5.3 TRPDIX1600 (16 channel bidirectional inputs only) Power 3.9VDC, 0.3W from OIS PLUS base model Approvals CE, UL Digital Inputs 14 Normal inputs (Bidirectional type) 2 High speed inputs Digital outputs N.A. Rated Input voltage 24VDC Rated Input Current Upto 5mA Input Impedance 4.9K ohm Minimum ON voltage...
  • Page 51 Wiring Diagram of TRPDIX1600 (16 channel bidirectional inputs only) 1. Wiring diagram for testing digital inputs (NPN Type): SW10 SW11 SW12 SW13 SW14 SW15 CO M CO M SW16 IP COM IP COM 24VDC 24VD C Closing Swx will turn on respective inputs 2.
  • Page 52: Trpro0012R (12 Channel Relay Outputs Only)

    2.5.4 TRPRO0012R (12 channel relay outputs only) Power 3.9VDC, 0.3W from OIS PLUS base model Approvals CE, UL Digital Inputs Digital outputs 12 Relay type outputs Rated Input voltage N.A. Rated Input Current N.A. Input Impedance N.A. Minimum ON voltage N.A.
  • Page 53 Wiring Diagram of TRPRO0012R Coil Supply 230 VAC 230 VAC 230 VAC 230 VAC *L1 to L12 are A.C. Load. Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 54: Trpdox0016

    2.5.5 TRPDOX0016 TRPDOX0016P(PNP Type transistor output) TRPDOX0016N (NPN Type transistor output) Power 3.9VDC, 0.3W from OIS PLUS base model Approvals CE, UL Digital Inputs Digital outputs 16 PNP type Transistor output. 16 NPN type Transistor output. Rated Input voltage 24VDC Rated Input Current Upto 5mA Input Impedance...
  • Page 55 Wiring Diagram of TRPDOX0016P: LOAD LOAD LOAD LOAD LOAD LOAD LOAD LOAD LOAD LOAD LOAD LOAD LOAD LOAD LOAD LOAD Wiring Diagram of TRPDOX0016N: LOAD LOAD LOAD LOAD LOAD LOAD LOAD LOAD LOAD LOAD LOAD LOAD LOAD LOAD LOAD LOAD Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 56: Trpaio202L (2 Ai, 2 Ao)

    2.5.6 TRPAIO202L (2 AI, 2 AO) Power 3.9VDC, 0.3W from FP base model Approvals CE, UL Analog Inputs 2 Inputs (4 to 20mA, 0 to 10V, -10 to +10V, 0 to 20mA) Analog Outputs 2 Outputs (4 to 20mA, 0 to 10V, 0 to 20mA) Analog Inputs Number of inputs Resolution...
  • Page 57 Wiring Diagram of TRPRTX0202L 1. Wiring diagram for analog voltage input: 2. Wiring diagram for analog current input: Analog + Voltage Output Analog Device Current 0 to 10V, Device + +/- 10V 4 to 20mA 1. Wiring diagram for analog voltage output: 2.
  • Page 58: Trpaio0400L (4 Ai)

    2.5.7 TRPAIO0400L (4 AI) Power 3.9VDC, 0.3W from OIS PLUS base model Approvals CE, UL Digital/Analog Inputs 4 Inputs (4 to 20mA, 0 to 10V, -10 to +10V, 0 to 20mA) Digital/Analog outputs N.A. Analog Inputs Number of inputs Resolution 12 Bit Voltage Mode: Input Range:...
  • Page 59 Wiring Diagram of TRPAIO0400L 1. Wiring diagram for analog voltage input: Analog Voltage Output Device 0 to 10V, +/- 10V 2. Wiring diagram for analog current input: Analog Current Output Device 0 to 20mA 4 to 20mA Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 60: Trpaio0402U-16 (4 Ai, 2 Ao)

    2.5.8 TRPAIO0402U-16 (4 AI, 2 AO) General Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 61 Wiring Diagram of TRPRTX0402 1. Wiring diagram for analog voltage input: IO2- PEA040 0 to 10V IN1+ 0 to 10V 0 to 5V IN3+ 0 to 5V IN1- IN3- COM1 COM3 0 to 10V 0 to 10V IN2+ IN4+ 0 to 5V 0 to 5V IN2- IN4-...
  • Page 62 3. Wiring diagram for RTD input: IO2- PEA040 PT100 IN1+ PT100 IN3+ PT1000 PT1000 IN1- IN3- COM1 COM3 PT100 PT100 IN2+ IN4+ PT1000 PT1000 IN2- IN4- COM2 COM4 4. Wiring diagram for analog millivolt input and thermocouple: IO2- PEA040 0 to 100V IN1+ 0 to 100V 0 to 50mV...
  • Page 63 1. Wiring diagram for voltage output: >1000Ω >1000Ω Voltage Voltage IO2- Output Output PEA040 IN1+ IN3+ IN1- IN3- COM1 COM3 IN2+ IN4+ IN2- IN4- COM2 COM4 2. Wiring diagram for current output <500Ω IO2- <500Ω Current Current Output Output PEA040 IN1+ IN3+ IN1-...
  • Page 64: Installation Instructions

    2.6 Installation Instructions The OIS PLUS should be mounted on a panel. A sealing gasket and mounting clamps are provided with each OIS PLUS unit for proper installation. Environmental Considerations: Make sure that the unit is installed correctly and that the operating limits are followed (see Specifications for OIS PLUS).
  • Page 65 Procedure to mount the unit: Gasket Mounting Hardw are Mounting Clamp Mounting Hardw are is a set of cap nut, screw & clamp Figure - 1 Figure - 2 Figure - 3 Figure - 4 Make a cut-out of the required size. Panel cut-out tolerance is +0.00mm. Put the gasket behind the bezel. The gasket may be sealed to the case using adhesive.
  • Page 66: Panel Cut-Out And Mounting For Ois60 & 70 Plus Models

    2.6.2 Panel Cut-out and Mounting for OIS60 & 70 PLUS Models Below given panel cut-out and mounting information is applicable to model with 5.7” & 7” LCD. Panel Cut-out Note: Maximum panel thick ness should be 6.5mm (Tolerance: +0.00mm). Procedure to mount the unit: Mounting Clamp Gasket...
  • Page 67 Figure - 3 Figure - 4 Make a cut-out of the required size. Panel cut-out tolerance is +0.00mm. Put the gasket behind the bezel. The gasket may be sealed to the case using adhesive. FIGURE - 1 There are four (4) slots provided on the unit case to top and bottom surface. FIGURE - 2 A set of four (4) mounting hardware is provided with each OIS PLUS5 unit.
  • Page 68: Panel Cut-Out And Mounting For Ois10 & 20 Plus Models

    2.6.3 Panel Cut-out and Mounting for OIS10 & 20 PLUS Models Below given panel cut-out and mounting information is applicable to model with 16x2 Multi color LCD. Dimensions: Panel Cutout: Below given panel cut-out and mounting information is applicable to model with 128X64 Multi color LCD (OIS40 PLUS Models: Dimensions: 118.5...
  • Page 69: Mounting For Clip-On I/O Modules

    2.6.4 Mounting for Clip-on I/O Modules Below given is the mounting informat ion applic able to expans ions with OIS PLUS base models. While unpacking the display. note the two (2) locking connectors. User can attach and detach the expansion model with the help of these locking connectors. While seen from both the sides of the expansion models.
  • Page 70 On the expansion case two slots are provided which rest on the base model back case as shown in the figure below: Here, the expansions rest with the base model. Then push down the locking connectors towards each-other. This will lock the expansion finally with the base model. Please note that along with these two joining (Locking connector as well slots), male connector from the expansion model will be insert into the female counter part on the base model termed as “EXPANSION PORT”.
  • Page 71 Mounting procedure of the expansion models with OIS PLUS models: The mounting procedure of the expansions with the OIS PLUS base models is as follows. Below given images will explore it more. Sep- 1: Sep- 2: Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 72 Step- 3:Final Product: Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 73: Power Supply Wiring Diagram

    2.7 Power Supply Wiring Diagram If wiring is to be exposed to lightening or other electrical surges, use appropriate surge suppression devices. Keep AC, high energy and rapidly switching DC wiring separate from signal wires. Connecting high voltages or AC power mains to the DC input will make unit unusable and may create an electrical shock hazard to personnel.
  • Page 74: Communication Ports

    2.8 Communication Ports OIS PLUS communication ports support four types of serial communications plus Ethernet. 2.8.1 Com Port 1: Available On: All OIS PLUS. It is an integrated RS-232 and RS-485/RS422 communication port. It communicates with external peripherals at baud rates of 4800 - 115.2Kbps with None, Even or Odd parity. RS485/RS422 connection can be used in multi drop communication network.
  • Page 75: Com Port 2

    Pin number Name Description TX + RS485 transmit + T X D RS232 transmit RX D RS232 receive RX + RS485 receive + Ground No connection No connection T X - RS485 transmit - RX - RS485 receive - 2.8.2 Com Port 2: Available On: OIS60 PLUS, OIS70E PLUS, &...
  • Page 76: Usb Device Port

    2.8.3 USB Device Port: Available On: All OIS PLUS. It is the same as a standard USB printer port. It can be used for programming and monitoring all OIS PLUS. Connector Used: Standard USB Type B female connector. It is a self-powered USB device, compliant with the USB 2.0 specification.
  • Page 77: Ethernet Port

    2.8.5 Ethernet Port: Refer to Ethernet User’s Manual, UM-OISPLUS-E003 Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 78: Basic I/O Allocation & Setup

    BASIC I/O ALLOCATION & SETUP ♦ I/O Allocation ♦ Setup Registers Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 79: I/O Allocation

    Different OIS PLUS displays have different types of I/O. No I/O: OIS12, OIS22, OIS40 PLUS, & OIS120A Fixed I/O: OIS10 PLUS & OIS20 PLUS Clip-on I/O: OIS40E PLUS, OIS55 PLUS, OIS60 PLUS, & OIS70E PLUS Three types of registers are associated with the I/O XW: Input Registers YW: Output Registers MW: Setup Registers...
  • Page 80 The I/O allocation for the OIS45E PLUS is shown below: For each slot (total of 3 for OIS45E PLUS) it describes: The name/part number of the I/O module. The address range of the I/O registers assigned to that module. A description of the I/O module. For the input module in slot 1, it shows that the 16 inputs are addressed as X01000 thru X01015.
  • Page 81: Setup Registers

    3.2 Setup Registers MW Register Allocation T able : Module MW Range T otal No Supported Base MW0000-MW0059 Expansion Slot 1 MW0100-MW0123 Expansion Slot 2 MW0200-MW0223 Expansion Slot 3 MW0300-MW0323 Expansion Slot 4 MW0400-MW0423 Expansion Slot 5 MW0500-MW0523 Setup Registers for Fixed I/O OIS PLUS For discrete inputs, the MW registers are used for setting up the high speed counter.
  • Page 82 Setup Registers for I/O OIS PLUS with Clip-on I/O MW Type Local CH1 Local CH2 HSC Configuration register MW0010 MW0020 High Speed Counter (HSC) Register MW0011 MW0021 MW0012 MW0022 HSC Preset Register MW0013 MW0023 MW0014 MW0024 HSC Enable Bit MW0015_0 MW0025_0 (M00240) (M00400)
  • Page 83 Setup Register Details Setup register MWssrr for the high speed counter is configured as shown below: When the appropriate setup register is configured as above, the inputs below are associated with high speed counter inputs. IO Type Base Expansion Input that Counts High Speed Pulses Output that Turns ON when Counter Reaches Preset Reset Input...
  • Page 84: High Speed Counter Inputs

    HIGH SPEED COUNTER INPUTS ♦ High Speed Counter Setup ♦ Single Phase Counter ♦ Quadrature Bi-Pulse Counter ♦ MW Register Table for High Speed Counter Modules Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 85: High Counter Setup

    4.1 High Counter Setup This chapter explains how to configure and use the HSC (High Speed Counter) inputs for the TRPHIO0808N and TRPHIO0808P clip on I/O modules. These modules have 4 HSC inputs. To configure the HSC inputs, follow the steps given below: 1.
  • Page 86 In this docker window, This option is “enabled”, by default. Once the user selects the HSC clip-on module, The default tags related to high speed counters will automatically be entered all as shown below: Using this tag database, a user can setup different modes of the HSC. Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 87: Single Phase Counter

    4.2 Single Phase Counter [MWssrr Mode Select Bits = 010] When the count input is changed from OFF to ON, the count value is increased by 1. When the count value reaches the set value, the count value is reset to 0. This counter operation is enabled while the HSC enable bit is ON.
  • Page 88 The chart below shows the value for which HSC can RUN in different modes. Normal Config HSC Condition Value in config register Normal Input HSC Single phase UP Counter Forced O/P ON preset reach Forced O/P OFF preset reach, ON when enable Quadrature 1X mode Forced O/P ON preset reach Forced O/P OFF preset reach,...
  • Page 89 6. Define count register, where user can see the counting. 7. Define Reset Bit [to reset the count number entered in PRESET”]. 8. Define forced output value [count once reach the value, user can set a output may be to ON/OFF LED or to start any process, etc.].
  • Page 90 9. When the value of high speed counter register reaches to value of preset register, then HSC Preset Reached bit will be ON. 10. Download the program to the HMI and enter the values with keypad on the screen. Related registers: Function Register/device Remarks...
  • Page 91: Quadrature Bi-Pulse Counter

    4.3 Quadrature Bi-pulse Counter In the Quadrature mode, input X2 is used along with X7. When the count value reaches the Preset, forced output will be activated and preset reached bit will be set ON. This counter operation is enabled while the soft- gate (HSC Enable bit) is ON.
  • Page 92 Related registers: Function Device/Register Remarks Phase A Count Input Channel Phase B Count Input Channel Reset Input Physical Reset Input Count Value MW0107 Data Range H0000 0000 to HFFF FFFF Preset MW0108 Set Count Value: Max = 4294967295 MW0109 Soft Gate M01076 Operation Enabled when Bit is ON Reset Bit...
  • Page 93: Mw Register Table For Hsc Expansion I/O Modules

    4.4 MW Register Table for HSC Expansion I/O Modules High speed inputs: Number of inputs: 4 Input channels: X0, X5, X2, X7 MW Type Expansion Slot 1 HSC Configuration register MW0100 MW0106 MW0112 MW0118 High Speed Counter (HSC) MW0101 MW0107 MW0113 MW0119 Register...
  • Page 94 MW Type Expansion Slot 4 HSC Configuration register MW0400 MW0406 MW0412 MW0418 High Speed Counter (HSC) MW0401 MW0407 MW0413 MW0419 Register MW0402 MW0408 MW0414 MW0420 HSC Preset Register MW0403 MW0409 MW0415 MW0421 MW0404 MW0410 MW0416 MW0422 HSC Enable Bit MW0405_0 MW0411_0 MW0417_0 MW0423_0...
  • Page 95: Pulse Width Modulated Outputs

    PULSE WIDTH MODULATED OUTPUTS ♦ Normal Mode PWM Output ♦ CW/CCW Mode PWM Output ♦ Pulse/DIR Mode PWM Output ♦ Fixed Pulse Mode PWM Output ♦ MW Register Table for PWM I/O Modules Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 96: Normal Mode Pwm Output

    This chapter explains how to configure and use the PWM (Pulse Width Modulated) outputs for the TRPHIO0808N and TRPHIO0808P clip on I/O modules. These modules have 1 PWM output. The PWM out can be setup for different modes of operation. This function is used to output a variable duty cycle pulse.
  • Page 97 6) Set 'On duty setting register' on screen and put its value as '10%' 7) Set enable flag resister on screen and set its status as 'ON". 8) Set 'Frequency setting error flag' on screen 9) Set 'On duty setting error flag' on screen 10) Download application This will RUN the operation in normal mode.
  • Page 98 The function selection is done through configuration registers as follows: Function Register / device Remarks Channel 1 PWM pulse Pulse enable flag M136_0 Output is enabled when ON Frequency setting register MW0125 Data range: 1 to 10000 MW0126 ON duty setting register MW0127 Data range: 0 to 100 MW0128...
  • Page 99: Cw/Ccw Mode Pwm Output

    5.2 CW/CCW Mode PWM Output To configure the high speed output in CW/CCW mode follow the steps below: 1) Create a new application. 2) Add a clip-on module in slot1 3) Set 'PWM configuration resister' on screen 4) Put value as 3 in 'PWM configuration resister' 5) Set 'frequency setting resister' on screen and put its value as '+5000' 6) Set enable flag resister on screen and keep its status as 'ON"...
  • Page 100 Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 101: Pulse/Dir Mode Pwm Output

    5.3 Pulse/DIR Mode PWM Output To configure high speed output in Pulse/DIR mode follow the steps below: 1) Create a new application 2) Add a clip-on module in slot1 3) Set 'PWM configuration resister' on screen 4) Put value as 7 in 'PWM configuration resister' 5) Set 'frequency setting resister' on screen and put its value as '+5000' 6) Set enable flag resister on screen and keep its status as 'ON"...
  • Page 102 Timing Diagram Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 103: Fixed Pulse Mode Pwm Output

    5.4 Fixed Pulse Mode PWM Output To configure high speed output in fixed pulse mode (Trapezoidal / soft start) follow the steps below: 1) Create a new application 2) Add expansion FPED-HS-0808N in slot1 3) Set 'PWM configuration resister' on screen 4) Put value as 9 in 'PWM configuration resister' 5) Set 'Minimum frequency setting resister' on screen and put its value as '4' 6) Set 'Maximum frequency setting resister' on screen and put its value as '100'...
  • Page 104 Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 105: Mw Register Table For Pmw I/O Modules

    5.5 MW Register Table for PMW I/O Modules MW Register Table: Function Register/device Remarks PWM pulse CH1 Expansion Y2 Configuration Register MW0124 Fixed pulse mode configuration register Pulse Out Enable MW0136_0 Bit ‘0’ is used for enable High speed output. (M01576) MIN Freq CH1 MW0125...
  • Page 106 High speed outputs: Number of outputs: 1 Output channels: Y2, Y4 MW Type Expansion Slot 1 Expansion Slot 2 Expansion Slot 3 CH1 (Y2) CH1 (Y2) CH1 (Y2) Configur MW0124 MW0224 MW0324 ation. Frequency MW0125 MW0225 MW0325 Setting register MW0126 MW0226 MW0326 ON duty...
  • Page 107 Configuration Register (Pulse/PWM Output): MWssrr Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 108: Analog Module Setup

    ANALOG MODULE SETUP ♦ Overview ♦ TRPAIO0400L (4 AI) ♦ TRPAIO0202L (2 AI, 2 AO) ♦ TRPRTX0402 (4 AI, 2 AO) Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 109: Overview

    6.1 Overview OIS PLUS clip-on analog modules can accept a number of different types of inputs and produce different types of outputs. To determine which type of input and which type of output the module used, a profile for the modules must be setup in the MW registers. The group of MW registers assigned to the module is determined by the modules mounting position.
  • Page 110: Trpaio0400L (4 Ai)

    6.2 TRPAIO0400L (4 AI) Analog Input Range: Set in MW register as defined in 6.1 for each channel used. Sr. No Input Range MW Setting for Input Range Type 4 to 20mA 0 to 10V -10 to 10V 0 to 20mA Analog Output Range: None 6.3 TRPAIO0202L (2 AI, 2 AO) Analog Input Range: Set in MW register as defined in 6.1 for each channel used.
  • Page 111: Trprtx0402 (4 Ai, 2 Ao)

    6.4 TRPRTX0402 (4 AI, 2 AO) Analog Input Range: Set in MW register as defined in 6.1 for each channel used. Input Range Input Type MW Setting for Input Range Type Voltage 0 to 10V 0 to 5V Millivolt 0 to 50mV 0 to 100mV 4 to 20mA 0 to 20mA...
  • Page 112 ♦ Downloading from USB Drive to OIS PLUS ♦ Uploading from OIS PLUS unit to USB Drive Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 113: Overview

    The USB host port can be used to perform a download or an upload of an application to or from a USB memory drive. This enables the user to update the OIS PLUS Series or download logging data without the use of a personal computer.
  • Page 114: Downloading From Usb Drive To Ois Plus

    4. Click YES to continue. There will be a slight pause. Please wait . . . Enumerating Memory Drive. 5. Click Download or Upload. 7.2 Downloading from USB Drive to OIS PLUS: In order to download an application from the USB memory drive to the OIS PLUS, the following files must be present in the USB Drive: Folder Name: “OIS55 PLUS”...
  • Page 115 3) Click APPLICATION to erase the old application and download the new application from the USB memory drive to the OIS PLUS. 4) The following message is displayed after downloading: Click OK to finish. Repeat step 3 and 4 for firmware and fonts. Note: This Download operation can be performed only when proper products folder is available in USB memory drive Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 116: Uploading From Ois Plus To Usb Drive

    7.3 Uploading from OIS PLUS to USB Drive: The following data can be uploaded from OIS PLUS unit to the USB drive: 1. Application 2. Firmware 3. Application + logged data 4. Application + Historical alarm data 5. Fonts 6. Ladder a) Connect the USB drive to the unit.
  • Page 117 d) The following message is displayed after uploading. Click OK to finish. Repeat step 3 and 4 if you need to upload any of the other options to the USB drive. Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 118: Usb Upload And Download

    USB UPLOAD AND DOWNLOAD ♦ Upload an Application ♦ Download an Application ♦ Device Information Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 119: Upload

    8.1 Upload An application can be uploaded from the OIS PLUS unit. To upload an application first select the appropriate communication port (serial or USB) for your computer by choosing “Communication | Com Port” menu option. T o reach this “Communication” docker window; choose “Project | Transfer | Upload”. Attach a computer to unit cable.
  • Page 120 In uploading, the application and the application plus logged data uploads can be performed. 1. Application If this option is selected, only the application will be uploaded from the unit. Note that tag and screen names can be uploaded only if the “Download tag names” option in “Project Con- figuration | Settings”...
  • Page 121: Download

    2 Port is either busy or does not exist This error occurs if you try to upload in unit while serial port is busy. 8.2 Download To download an application into the unit, either click on “Download” button from the T ool station or choose “Project | Transfer”...
  • Page 122 Com Port – Used to select which communication port to use for downloading. By default Com1 is selected. Any changes are stored with the OIS PLUS program. Download Options 1. Application Select this option to download the application to the unit. 2.
  • Page 123: Device Information

    8.3 Device Information Device information is used to detect the information such as model name, bootblock / hardware / firmware version of base and expansion models as well as user can upgrade firmware of expansion modules. User can select device information from menu View -> Device Information: Expansion Firmware Upgrade Scheme: If the firmware version present in connected expansion module is lower as compared to the one present in latest OIL-DS Build, the user if required can upgrade the firmware version of the connected expansion module.
  • Page 124: Usb Driver Installation

    USB DRIVER INSTALLATION Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 125: Usb Driver Installation Guide

    9.1 USB Driver Installation Guide Please follow the steps to install the USB driver for TRP Series HMI. Power on the HMI without connecting USB cable to it. Use USB A to B cable to connect HMI to PC. Connect B type end of cable to HMI Connect A type end of cable to PC 1 2 3 4 After connecting cable, PC will detect the HMI and will show pop up message on system tray.
  • Page 126 Following window will appear: Select Click to continue. Following window will appear: Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 127 Select the option and click to continue. Following screen will appear: Select “Show All Devices” and click Next Following screen will appear: Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 128 Select utton, which will open a dialogue box as shown below: The USB drivers are provided in the TR PGM software. Click o and select the path …\Installed Directory\USB Drivers Click Following window will appear: Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 129 Select from Model and Click to continue. The driver installation will start with following warning: Click on to continue installation. Windows will automatically create a system restore point and will install the driver. After complete installation following window will appear: Click on to end installation.
  • Page 130: Cannot Install The Hmi Usb Driver

    All OIS PLUS have at least one Com port. The OIS PLUS can be programmed and monitored thru the COM 1 port using the serial cable IBM-0909-1-00. This cable can be purchased from Toshiba or made as follows: Computer Side OIS PLUS Side connect any other wires than those shown above.
  • Page 131 Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...

Table of Contents