Huawei NetCol5000-C Series User Manual page 81

Simple configuration in-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C Series:
Table of Contents

Advertisement

NetCol5000-C030 In-row Chilled Water Smart Cooling
Product
User Manual (Simple Configuration)
Figure 3-46 Connecting T/H sensors
(1) T/H sensor location in the cold aisle
Step 2 Set the DIP switch on the T/H sensor. For details, see
Table 3-7 DIP switch settings for T/H sensors
Position
Address
Cold aisle
11
12
13
Hot aisle
21
Issue 09 (2020-01-10)
A T/H sensor cable is 10 m long and must be bound with cable ties near a server air intake vent and
about 1.5 m (33U) above the floor.
Each smart cooling product supports up to three T/H sensors in the cold aisle and the other three in
the hot aisle at most.
Name
No. 1
Cold aisle 1
ON
T/H
Cold aisle 1
OFF
T/H
Cold aisle 1
ON
T/H
Hot aisle 1
ON
T/H
Copyright © Huawei Technologies Co., Ltd.
(2) T/H sensor location in the hot aisle (optional)
Table
3-7.
No. 2
No. 3
No. 4
ON
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
OFF
3 Installation
No. 5
No. 6
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
72