Connecting The Water Inlet Or Outlet Pipes - Huawei NetCol5000-C Series User Manual

Simple configuration in-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C Series:
Table of Contents

Advertisement

NetCol5000-C030 In-row Chilled Water Smart Cooling
Product
User Manual (Simple Configuration)

3.11.3 Connecting the Water Inlet or Outlet Pipes

Context
Procedure
Step 1 Wrap the water inlet or outlet pipe with thermal insulation foam.
Step 2 Cut a cross in the hole rubber ring and route the pipe through the rubber ring to a position
close to the reserved port.
Step 3 Insert the lower end of the water pipe adapter into the rubber hose, and tighten the hose clamp
using a 5 mm hex key.
Issue 09 (2020-01-10)
b.
Connect an adapter to the reserved port on the equipment, as shown by (2) in
3-30.
c.
Connect the PPR or aluminum plastic pipe to the adapter, as shown by (3) in
3-30
Seal the screw thread with thread sealant.
d.
Connect the automatic condensate drainpipe to the condensate drainage port in the
equipment room. Seal the joint with thread sealant. The required torque is 25 N· m.
e.
Fully wrap the drainpipe with thermal insulation foam.
A Y-shaped strainer has been installed on the chilled water inlet.
Connect the water inlet or outlet pipes from the inside to the outside and from the bottom
to the top.
Figure 3-9
shows how to connect water inlet and outlet pipes. The following uses
method A as an example.
Copyright © Huawei Technologies Co., Ltd.
3 Installation
Figure
Figure
58