Siemens RXB Series Basic Documentation page 37

Knx bus communications
Table of Contents

Advertisement

Setting values
Note
Example
Sends the
remotely set
time of day:
10:24
Clock time operation:
Master
Time in the
QAW740 room unit
For internal use only
Siemens
Building Technologies
Rem set clock slave: Yes The time slave transmits the remote time and/or date
Rem set clock slave: No Time slaves with this setting can only receive the time
All time slaves can operate with the default setting "Rem set clock slave: Yes".
However, it is also possible for only one time slave (or none) to operate with this
value.
Receives:
10:24
Remotely set
time of day: 10:24
Clock time operation:
Slave
Rem set clock slave: Yes
For its timer functions, the QAW740 room unit requires the time from the time
master. It can receive the time over the KNX bus subject to the following criteria:
A bus device must be defined as the time master (setting "Clock time op:
Master").
The QAW740 room unit is connected to an RM... controller via a "Geogr. Zone
(apartm.)". For communication and filtering purposes (see Section 8.2), the time
master and the room unit should be in the same "Geogr. Zone (apartm.)".
However, this is not mandatory.
The room unit must have received the time from the time master. Note: The time
master transmits the time only every 10 minutes.
QAW740
Time of day
Room unit receives
time of day for timer
function
Geogr zone: 5
KNX bus communications
Basic communication settings
settings to the time master. The time master transmits the
values received to all time slaves (including any remotely
adjustable slave(s).
and date from the time master.
Receives:
10:24
Clock time operation:
Clock time operation:
Slave
Autonomous
Uhrzeit
Time of day
Clock time operation:
Master
Geogr zone: X
Has its own
Receives:
time of day
Time day for
timer function
RM..
Time of day
Clock time operation:
Slave
Geogr zone: 5
10:24
RM..
37 / 88
CE1P3127en
2013-04-08